Connect the Power Terminal

The chassis provides redundant power terminal inputs. Two sources of –48 VDC must be 
provided to use the redundant power feature. The two power inputs are labeled  –48V A  and 
–48V B
NOTE
A readily accessible disconnect device such as a rackmount fuse and alarm
panel that is suitably approved and rated, should be incorporated in the fixed
wiring.
NOTICE
The Total Access 5000 System is designed for a reliably grounded ‐48V
nominal DC supply. This requires the positive terminal to be referenced to
earth ground. Make this reference connection at either the source (rectifier or
battery) or at the frame. Powering by any other means may void the warranty
of the product.
To connect power to the chassis, complete the following:
1. Determine which fuse pairs are to supply power to the Total Access 5000 shelf and 
2. Ensure the power is disconnected at the source.
3. Open the plastic power terminal doors on the rear of the chassis to access the power 
4. Cut four lengths of appropriately sized wire to reach from the terminals on the fuse and 
5. Strip 5/8 of an inch from the power and return wires, and using a crimping tool, connect 
6. Connect the ends of one wire between the "A‐Side" CO –48 VDC supply and the "A‐
7. Connect three more power wires as follows:
8. Ensure all power connections are tight.
9. Close the plastic power terminal doors.
65K510DEP08-1A
 and are located on the back of the chassis (see Figure 2‐6).
remove the fuses from the A and B slots for the pair.
terminals.
alarm panel to the power terminals on the Total Access 5000 Chassis. Leave enough slack 
in the wires to allow for dressing the wires to the rack according to local practice.
an appropriate lug to each end of the wires.
Side" 
–48V A
 terminal on the Total Access 5000 Chassis.
• "A‐Side" CO –48 VDC return to chassis "A‐Side"  RTN
• "B‐Side" CO –48 VDC supply to chassis "B‐Side"  –48V B
• "B‐Side" CO –48 VDC return to chassis "B‐Side"  RTN
Section 2, Installation - Connect the Power Terminal
2-9