Disable Power Feed Alarms

To disable the power feed alarms, complete the following:
NOTE
A power feed input cannot be disabled, but if both interfaces are not being
sourced with ±48 VDC or ±24 VDC powering, there is a power fail alarm
active for the unused input.
1. From the Enable prompt, type  configure terminal , and press  E
2. From the Global Configuration prompt, access the system alarm prompt by typing 
3. If power feed A is unused, disable the power feed A alarm by typing  no alarm enable
4. If power feed B is unused, disable the power feed B alarm by typing  no alarm enable
5. Type  end , and press  E
The power A or B fail alarm should be cleared in the alarm log.
Once all unused interfaces are disabled, the alarms for these interfaces should now be cleared. 
If all in‐use interfaces (DS3, Ethernet, Gigabit‐Ethernet, and power) are in non‐alarmed states, 
then the Alarm LED on the NetVanta 800 should now be lit solid green.

Clear the Alarm Log

Before clearing the Alarm Log, the alarms must first be acknowledged.
To clear the Alarm Log, complete the following:
1. From the Enable prompt, type  force alarm acknowledge , and press  E
2. Clear the alarm log by typing  force alarm clear  and pressing  E
3. Verify there are no alarms by typing  show alarm log  and pressing  E

Save the NetVanta 800 Provisioning

After any changes are made, whether new services or port configuration, the user should 
always save provisioning to non‐volatile memory in order to maintain those attributes during 
power loss. From the Enable prompt, save provisioning by typing  copy running-configu-
ration startup-configuration
The save completes within 5‐seconds and returns to the user prompt immediately. Once the 
user prompt returns, the NetVanta has saved its configuration to non‐volatile memory.
6-30
bal Configuration prompt.
, and press  E
system-alarm
, and press  E
power-fail dc a
, and press  E
power-fail dc b
NTER
NTER
.
NTER
.
NTER
.
 to return to the Enable prompt.
, and press  E
NTER
.
NTER
 to access the Glo‐
NTER
.
NTER
.
NTER
.
65K510DEP08-1A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ta 5000

Table of Contents