Generic Timer & Counter - ABB ACS880 Firmware Manual

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
133
133 Generic timer &
counter
133.01
Counter status
Bit
Name
0
Ontime1
1
Ontime2
2
Edge1
3
Edge2
4
Value1
5
Value2
6...15
Reserved
0000h...FFFFh
133.10
On-time 1 act
0 ... 4294967295 s
133.11
On-time 1 limit
0 ... 4294967295 s
133.12
On-time 1 func
Bit
Function
0
Counter mode
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds
1 = Saturate: If warning is enabled by bit 1, it stays active until reset
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning is given when the limit is reached
2...15
Reserved
0000h...FFFFh
133.13
On-time 1 src
False
True
RO1
Other [bit]
133.14
On-time 1 warn sel
On-time 1
Device clean
Add cool fan
Description
Configuration of maintenance timers/counters.
See also section
Maintenance timers and counters
30).
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have
exceeded their limits.
This parameter is read-only.
Description
1 = On-time timer 1 has reached its preset limit.
1 = On-time timer 2 has reached its preset limit.
1 = Signal edge counter 1 has reached its preset limit.
1 = Signal edge counter 2 has reached its preset limit.
1 = Value counter 1 has reached its preset limit.
1 = Value counter 2 has reached its preset limit.
Maintenance time/counter status word.
Reading of on-time timer 1. Can be reset from the Drive
composer PC tool, or from the control panel by keeping
Reset depressed for over 3 seconds.
Reading of on-time timer 1.
Sets the warning limit for on-time timer 1.
Warning limit for on-time counter 1.
Configures on-time timer 1. This timer runs whenever
the signal selected by parameter
on.
After the limit set by
133.11 On-time 1 limit
the warning specified by
given (if enabled by this parameter), and the timer reset.
The current value of the timer is readable from
parameter
133.10 On-time 1
status
indicates that the time has exceeded the limit.
On-time timer 1 configuration word.
Selects the signal to be monitored by on-time timer 1.
Constant 0.
Constant 1.
Bit 0 of
110.21 RO status
Source selection (see
Terms and abbreviations
39).
Selects the warning message for on-time timer 1.
AE45 On-time
1.
AE4B Device clean
warning.
AE4F Additional cooling fan
133.13 On-time 1 src
is reached,
133.14 On-time 1 warn sel
act. Bit 0 of
133.01 Counter
(page 55).
warning.
Parameters 103
Def/FbEq16
(page
-
1 = 1
-
1 = 1 s
0 s
1 = 1 s
00b
is
is
1 = 1
False
0
1
2
on page
-
On-time 1
0
6
7