332 Parameters
No.
Name / Range /
Selection
33
Generic timer &
counter
33.1
Counter status
b0
On-time 1
b1
On-time 2
b2
Edge 1
b3
Edge 2
b4
Value 1
b5
Value 2
b6...15
Reserved
0000h...FFFFh
33.10
On-time 1 actual
0...4294967295 s
33.11
On-time 1 warn limit
0...4294967295 s
33.12
On-time 1 function
b0
Counter mode
b1
Warning enable
b2...15
Reserved
0000h...FFFFh
33.13
On-time 1 source
False
Description
Configuration of maintenance timers/counters.
See also section
Maintenance timers and
counters (page
118).
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have
exceeded their limits.
This parameter is read-only.
1 = On-time timer 1 has reached its preset limit.
1 = On-time timer 2 has reached its preset limit.
1 = Signal edge counter 1 has reached its preset limit.
1 = Signal edge counter 2 has reached its preset limit.
1 = Value counter 1 has reached its preset limit.
1 = Value counter 2 has reached its preset limit.
Displays the actual present value of on-time timer 1.
The timer runs whenever the signal selected by
parameter
33.13 On-time 1 source
When the timer exceeds the limit set by
1 warn
limit, bit 0 of
33.1 Counter status
warning specified by
33.14 On-time 1 warn message
also given if enabled by
The timer can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
Actual present value of on-time timer 1.
Sets the warning limit for on-time timer 1.
Warning limit for on-time timer 1.
Configures on-time timer 1.
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 0 of 33.1) switches to 1 for one
second. The warning (if enabled) stays active for at
least 10 seconds.
1 = Saturate: When the limit is reached, the counter
status (bit 0 of 33.1) switches to 1, and remains so until
33.10
is reset. The warning (if enabled) also stays active
until
33.10
is reset.
0 = Disable: No warning is given when the limit is
reached
1 = Enable: A warning (see 33.14) is given when the limit
is reached
Selects the signal to be monitored by on-time timer 1.
Constant 0 (timer disabled).
is on.
33.11 On-time
is set to 1. The
33.12 On-time 1
function.
Def / Type
FbEq 16b / 32b
- / uint16
1 = 1
- / uint32
is
- / -
- / uint32
- / -
- / uint16
1 = 1
False / uint32
0