Nortel DMS-100 Series Replacement Procedures page 522

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-490 XPM card replacement procedures (continued)
NTBX02
in an RSC-S (PCM-30) Model A RCO2
At the RCE frame
21
22
297-8021-547 Standard 14.02 May 2001
CAUTION
Static discharge may cause damage to circuit packs
Put on a wrist strap and connect it to the frame of the RMM
before removing any cards. This protects the RMM against
service degradation caused by static electricity.
DANGER
Equipment damage
Take these precautions when removing or inserting a card:
1. Do not apply direct pressure to the components.
2. Do not force the cards into the slots.
Put on a wrist strap.
Remove the NTBX02 card as shown in the following figures.
a
Locate the card to be removed on the appropriate shelf.
b
Open the locking levers on the card to be replaced and gently pull the
card toward you until it clears the shelf.
(continued)