Nortel DMS-100 Series Replacement Procedures page 1005

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

16
Power up the inactive RCC2 unit as follows:
a
Ensure that the power converter (NTMX72) is fully inserted. A major
audible alarm may sound. This alarm is silenced when power to the
NTMX72 circuit card is restored.
Note:
b
If the power converter is an NTMX72AA, set the switch on the power
converter to the Reset position. Set the associated circuit breaker on the
FSP to the ON position.
If both the converter FAIL LED and FRAME FAIL lamp on the FSP go
OFF, go to step 17.
If both the converter FAIL LED and FRAME FAIL lamp on the FSP do not
go OFF, hold the switch on the NTMX72AA converter in the Reset
position and simultaneously set the associated circuit breaker on the FSP
to the ON position. Both the converter FAIL LED and FRAME FAIL lamp
on the FSP will go OFF. Go to step 17.
c
If the power converter replaced is an NTMX72AB set the associated
circuit breaker on the FSP to the ON position for the NTMX72AB that was
powered down in step 12. Both the converter FAIL LED and FRAME FAIL
lamp on the FSP will go OFF. Go to step 17.
17
After replacing the faulty card, load the inactive RCC2 unit by typing
>LOADPM
and pressing the Enter key.
where
unit_no
is the number of the inactive RCC2 unit
If load
passed
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
in an RSC-S (DS-1) Model A RCC2
UNIT
unit_no
Do
step 18
1-973
NTMX72
(continued)