Nortel DMS-100 Series Replacement Procedures page 129

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

in an RSC-S (PCM-30) Model A RCO2
Replacing an NT6X92 card in an RSC-S RCO2
At your Current Location
1
Proceed only if you have been directed to this card replacement procedure
from a step in a maintenance procedure, are using the procedure for verifying
or accepting cards, or have been directed to this procedure by your
maintenance support group.
2
Obtain an NT6X92 replacement card. Ensure the replacement card has the
same product equipment code (PEC), including suffix, as the card that is to
be removed.
3
Ensure the PM level of the MAP display is currently displayed and the RCO2
is posted by typing
>MAPCI;MTC;PM;POST RCO2 rco2_unit_no
and pressing the Enter key.
where
rco2_unit_no
is the number of the RCO2 with the faulty card
Example of a MAP display:
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
CAUTION
Loss of service
When replacing a card in the RCO2, ensure that the unit in
which you are replacing the card is inactive and that the mate
unit is active.
1-97
NT6X92
(continued)