Nortel DMS-100 Series Replacement Procedures page 392

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-360 XPM card replacement procedures (continued)
NTAX78
in an SMA
(continued)
15
16
At the MAP terminal
17
18
At the equipment frame
19
20
297-8021-547 Standard 14.02 May 2001
Use the following information to determine the next step.
If you were directed here from
alarm clearing procedures
other
Reset the unit by typing
>PMRESET UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the inactive SMA unit (0 or 1)
Load the inactive SMA unit by typing
>LOADPM UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the busied SMA unit
If load
passed
failed
Return the inactive SMA unit to service by typing
>RTS UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the SMA unit loaded in step 17
If RTS
passed
failed
Remove the sign from the active SMA unit.
Go to the common returning a card procedure in this document.
Do
step 19
step 16
Do
step 18
step 21
Do
step 19
step 21