Services
d. (Optional) Enable the gateway to send broadcast messages to this client:
(config service modbus_gateway client test_modbus_client)> broadcast
true
(config service modbus_gateway client test_modbus_client)>
e. Set the maximum time to wait for a response to a message:
(config service modbus_gateway client test_modbus_client)> response_
timeout value
(config service modbus_gateway client test_modbus_client)>
Allowed values are between 1 millisecond and 700 milliseconds, and take the format
numberms.
For example, to set response_timeout to 100 milliseconds:
(config service modbus_gateway client test_modbus_client)> response_
timeout 100ms
(config service modbus_gateway client test_modbus_client)>
The default is 700ms.
Digi Connect EZ Mini User Guide
ii. Set the port:
(config service modbus_gateway client test_modbus_
client)> serial port
(config service modbus_gateway client test_modbus_
client)>
ii. Set the packet mode:
(config service modbus_gateway client test_modbus_client)>
serial packet_mode value
(config service modbus_gateway client test_modbus_client)>
where value is either rtu or ascii. The default is rtu.
iii. Set the maximum allowable time between bytes in a packet:
(config service modbus_gateway client test_modbus_client)>
serial idle_gap value
(config service modbus_gateway client test_modbus_client)>
where value is any number between 10 milliseconds and one second, and take
the format number{ms|s}.
For example, to set idle_gap to one second, enter 1000ms or 1s.
iv. (Optional) Enable half-duplex (two wire) mode:
(config service modbus_gateway client test_modbus_client)>
serial half_duplex true
(config service modbus_gateway client test_modbus_client)>
Modbus gateway