Harmonics controller

Description
Harmonics in the line voltage cause harmonics in the line currents. Current harmonics can
be reduced by activating the harmonics controller.
Example: setting the harmonics controller
The 5th and 7th harmonics are to be compensated:
Table 1- 4
Index
[0]
[1]
The phase currents in parameter p0069[0..2] (U, V, W) can be checked using the STARTER trace
function.
Overview of important parameters (see the SINAMICS S120/150 List Manual)
● p3624[0...1] Infeed harmonics controller order
● p3625[0...1] Infeed harmonics controller scaling
● r3626[0...1] Infeed harmonics controller output
● r0069[0..6] Phase current, actual value
1.2
Smart Infeed
Features
● For Smart Line Modules with a power of ≥ 16 kW
● Unregulated DC link voltage
● Regenerative feedback capability
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Example parameters for the harmonics controller