Figure 23: Wago-I/O-Pro Project With Integrated "Wagolibhart_0X.lib" Library - WAGO I/O-SYSTEM 750 Manual

2ai 4-20ma hart ex i 2-channel analog input; hart; intrinsically safe, 2ai 4-20ma hart ne43 ex i 2-channel analog input; hart; namur ne43; intrinsically safe
Table of Contents

Advertisement

68
Commissioning
1.
Launch WAGO-I/O-CHECK and set the operating mode to "2 AI + 6-byte
mailbox".
Proceed as described in the Section "Operating Modes" > ... > "Setting via
WAGO-I/O-CHECK".
WAGO-I/O-CHECK up to Version 3.17.1.17:
Setting Limitations for PROFIBUS Operating Modes
For the PROFIBUS operating modes "1, 2, 3 or 4 HART variable(s) per channel",
switching via WAGO-I/O-CHECK and operation on a fieldbus coupler other than
a PROFIBUS fieldbus coupler (750-333) or controller (750-833) is not currently
possible. A HART I/O module set up for HARD dynamic variables using GSD
files can therefore currently only be operated with a PROFIBUS fieldbus coupler
(750-333) or controller (750-833).
It is then possible to restore the default state of the HART I/O module using
WAGO-I/O-CHECK and the PROFIBUS fieldbus coupler (750 333) or controller
(750-833). Make sure that the PROFIBUS fieldbus coupler (750-333) or
controller (750-833) is not parameterized using GSD files.
2.
Launch WAGO-I/O-PRO CAA, select the Resources tab and double-click
in the tree structure on Library Manager to open the respective dialog.
Integrate the "WagoLibHART_0x.lib" library for your "IEC 61131-3" project.
You can then access the HART commands directly in your project and
execute these locally from your "IEC 61131-3" application.

Figure 23: WAGO-I/O-PRO Project with Integrated "WagoLibHART_0x.lib" Library

Manual
Version 1.4.0
WAGO-I/O-SYSTEM 750
750-484 2AI 4-20mA HART Ex i