Specifications - BeaconMedaes MedPlus TotalAlert Operation And Maintenance

Alarm network
Table of Contents

Advertisement

Specifications

For MedPlus TotalAlert® Alarm Network specifications, refer to table 1-10 on
page 1-41 through table 1-15 on page 1-42.
Refer to table 1-16 on page 1-43 for the types of existing alarms that can be con-
verted to a MedPlus TotalAlert® Alarm Network—Master Alarm, MedPlus
TotalAlert® Alarm Network—Area Alarm, or MedPlus TotalAlert® Alarm
Network—Combination Alarm. Also included in the table are the sizes that the
existing rough-in boxes need to be, and the conversion kits that replace those
existing alarms.
Facility Power Specifications
Supply voltage for single power supply alarms 120 V AC, 60 Hz
Breaker for single power supply alarms
Supply voltage for dual power supply alarms
Breaker for dual power supply alarms
Field power supply wiring
Fuse rating for internal power supply (except
for the Master Alarm plus Six Area Alarm
Modules)
Fuse rating for internal power supply on the
Master Alarm plus Six Area Alarm Modules
Table 1-11. Cabling Requirements from the Area Alarm Module to the

Specifications

Distance
Cable
Signal Power
MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Table 1-10. Power Specifications
15 A
120 V AC, 60 Hz
15 A
12 gauge
0.5 Amp Slo-Blo®a
0.75 Amp Slo-Blo®
Transducer
Maximum 4500' (1372 m)
Stranded, 22-gauge, shielded, twisted-
pair, three-conductor cable
15 V DC, 75 mA maximum
Specifications
Chapter 1: Introduction
Ratings
Dimensions
Page 1-41