Do you have a question about the MedPlus TotalAlert and is the answer not in the manual?
Questions and answers
Rocco Sylvester
January 23, 2025
I an looking for a circuit board for one of your products. The # on the circuit board is, HCRB-0000-0000/D205504 where can I get one?
Rocco Sylvester
January 23, 2025
I found a PC board in a manual. How do I get one.
1 comments:
Mr. Anderson
February 10, 2025
Contact BeaconMedæs Technical Support for information on obtaining a PC board for the MedPlus TotalAlert system.
This answer is automatically generated
Rocco Sylvester
January 23, 2025
The PC board I **** looking for is Area Alarm Communications Board
1 comments:
Mr. Anderson
May 14, 2025
The Area Alarm Network Communications Board for the BeaconMedaes TotalAlert provides the same functions as the Area Alarm Connector P.C. Board and also connects to the facility’s Ethernet. This connection allows optional communication with the Master Alarm, enabling it to monitor the Area Alarm.
This answer is automatically generated
Tony Brodie
February 2, 2025
Med plus total alert I **** getting a A 03 on Oxygen panel
1 comments:
Mr. Anderson
February 10, 2025
An A03 error on the Oxygen panel of the BeaconMedæs MedPlus TotalAlert indicates a Transducer Communication Error. It suggests that the transducer may not be connected properly. The troubleshooting steps involve checking the connection, and if the issue persists, replacing the transducer.
This answer is automatically generated
Ed Leininger
April 21, 2025
Regarding My Medplus Total Alert area alarm I need to replace the transducer P6819
Additional info. from the transducer HRTM-RETR-NTRG/206261-N
2 comments:
Ed Leininger
April 21, 2025
@Ed Leininger Need to order the replacement transducer
Mr. Anderson
May 11, 2025
To replace the transducer P6819 for the BeaconMedæs MedPlus TotalAlert area alarm, follow these steps:
1. Check if the transducer shows a slow steady flash on its heartbeat LED. If yes, replace the transducer. 2. Ensure the transducer is connected properly. If not, reconnect it properly. 3. Inspect the transducer wiring for pinching. If wiring is pinched, replace the transducer wiring. 4. If the issue persists after these steps, replace the transducer following procedure 4.23 (referenced on page 4-62 of the manual).
Always disconnect power before servicing and follow standard safety procedures.
This answer is automatically generated
Subscribe to Our Youtube Channel
Related Manuals for BeaconMedaes MedPlus TotalAlert
Page 2
Windows® a registered trademark of Microsoft Corporation. The information contained in this manual is subject to change without notice. BeaconMedæs makes no commitment to update or keep current, the information contained in this manual. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page i...
Page 3
To order additional copies of this manual, call BeaconMedæs Technical Support at 1-888-4MEDGAS (1-888-463-3427), and order part number 205728. Page ii MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Detailed Component Descriptions................1-21 Master Alarm ....................1-21 Configuring Options Available for the Master Alarm........1-24 Building Automation System (N2) Mapping ..........1-26 Area Alarm ....................1-30 Configuring Options Available for the Area Alarm ........1-33 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page iii...
Page 5
Transfer Configuration ..................1-96 Browse Active MedPlus TotalAlert® Alarm Network Inputs ......1-98 Browse the Event Log ..................1-99 Browse Alarm Network Devices..............1-100 Browse Device Information ................1-101 Browse Master Alarm’s Diagnostics Menu............1-102 Page iv MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 6
Initial Actions ......................2-4 Function Checks ......................2-5 Master Alarm Self-Test ..................2-5 Area Alarm Self-Test....................2-6 Local Alarm Self-Test ..................2-6 Final Actions.......................2-7 Error Codes and Troubleshooting Tips ..............2-8 Area Alarm ......................2-8 Master Alarm ......................2-9 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page v...
Page 7
No Display on One Area Alarm Module..............2-36 Audible Signal Does Not Silence................2-36 No Audible Signal on the Master Alarm..............2-37 No Audible Signal on the Area Alarm ..............2-37 No Audible Signal on the Local Alarm..............2-38 Page vi MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 8
Master Alarm and Area Alarm Front Panels (not Including Area Alarm Modules)......................4-6 Removal........................4-6 Replacement ......................4-9 Master Alarm Module ....................4-10 Removal......................4-10 Replacement .......................4-11 Master Alarm Battery ....................4-12 Removal......................4-12 Replacement .......................4-13 Master Alarm Breakout P.C. Board................4-14 Removal......................4-14 Replacement .......................4-15 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page vii...
Page 9
Local Alarm Front Panel ..................4-32 Removal......................4-32 Replacement .......................4-33 Local Alarm P.C. Board....................4-34 Removal......................4-34 Replacement .......................4-35 Local Alarm Transformer ..................4-36 Removal......................4-36 Replacement .......................4-37 Local Alarm Buzzer Assembly.................4-38 Removal......................4-38 Replacement .......................4-39 Power Supply Fuse....................4-40 Removal......................4-40 Page viii MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 10
Conversion Kit Housed in the Area Line Pressure Alarm (0321) Rough-In Box from BeaconMedæs, Hill-Rom, or Medæs Only .....4-58 Removal......................4-58 Replacement .......................4-60 Remote-Mount Transducer..................4-62 Removal......................4-62 Replacement .......................4-63 Local-Mount Transducer ..................4-64 Removal......................4-64 Replacement .......................4-66 Internet Connections....................4-68 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page ix...
Page 11
Setting up the Internet Interface ................6-11 Ethernet Details ....................6-13 Physical Connection ..................6-13 Addressing on a Managed Network.............6-13 Addressing on an Un-Managed Network.............6-13 Discovery......................6-17 Accessing......................6-17 Serial Port (PPP) Details ..................6-19 Physical Connection ..................6-19 Page x MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 12
NULL Modem Driver Setup Instructions for Windows® Operating System ........................6-20 Dial-Up Configuration ..................6-21 Serial Port (PPP) Connection ................6-22 Master Alarm Module or Network Communications Board Connection......................6-23 Multiple MedPlus TotalAlert® Alarm Network Systems in the Same Facility ........................6-24 General Information ....................6-25 Repair ........................6-25 Test........................6-27 Calibration ......................6-27 Cleaning........................6-28...
Page 13
Table of Contents NOTES: Page xii MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 14
Area Alarm ....................1-15 Area Alarm Rough-In Assembly ..............1-17 Area Alarm Front Panel ................1-18 Local Alarm ....................1-19 Detailed Component Descriptions................1-21 Master Alarm ....................1-21 Configuring Options Available for the Master Alarm........1-24 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-1...
Page 15
Set Master Alarm’s Clock ..................1-92 Configure the Alarm Network Settings..............1-94 Clear Alarm Network Device List..............1-95 Transfer Configuration ..................1-96 Browse Active MedPlus TotalAlert® Alarm Network Inputs ......1-98 Browse the Event Log ..................1-99 Page 1-2 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 16
Browse List of Masters ..................1-126 Browse Event Log ....................1-127 Browse Area Alarm’s Communications Statistics..........1-128 Local Alarm Setup Procedures................1-129 Local Alarm Labeling.....................1-129 Local Alarm Power-Up...................1-132 Safety Tips ......................1-133 Warning and Caution Labels ..................1-140 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-3...
Chapter 6: General Procedures Cleaning, preventive maintenance, and other general procedures are described in this chapter. Chapter 7: Accessories Chapter 7 lists the accessories for the MedPlus TotalAlert® Alarm Network. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-5...
– A CAUTION points out special procedures or precautions that per- sonnel must follow to avoid equipment damage. • The symbol below highlights an ELECTRICAL SHOCK HAZARD WARN- ING: Figure 1-2. Electrical Shock Hazard Warning Page 1-6 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
• Selected vacuum pump operating conditions • Selected manifold operating conditions The MedPlus TotalAlert® Alarm Network is available in two types of configura- tions: one for installation into new construction and one for installation into a remodeling project or an alarm system upgrade. For the purposes of this manual, the first configuration type is called the “original”...
If the Network Communications Board is installed in the Area Alarm, the Master Alarm can monitor the operation and condition of MedPlus TotalAlert® Area Alarm Modules. There are two dry-contact relays featured on the Master Alarm that provide signals to outputs.
Page 22
They convert these signals and display the actual pressure or vacuum in either English or metric units, as specified by the customer. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-9...
Page 23
The MedPlus TotalAlert® Alarm Network Conversion Kits operate the same as the original alarm network. 17. Transducer—Transducers connect to the supply piping with DISS gas-spe- cific demand valves and transmit the actual line pressure or vacuum to the appropriate Area Alarm Module.
Display (AU)—Displays alarm status. LED indicators (AV)—Light either green or red depending on the • alarm status. Label (AW)—Shows which type of gas being indicated by the LED. • MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-11...
Page 25
NOTE: The MedPlus TotalAlert® Alarm Network Conversion Kit is shipped with a frame. The frame is surface-mounted to the dry wall around the existing rough-in box. Then, the front panel mounts to the frame.
The mounting brackets are not attached when they are shipped. Attach them before installation. For more information about installing an original alarm net- work, refer to the MedPlus TotalAlert® Alarm Network Installation Instructions. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Features Chapter 1: Introduction When installing the MedPlus TotalAlert® Alarm Network Conversion Kit, the Breakout P.C. Board and the power supply assembly mount in the existing alarm’s rough-in box. The conversion kit power supply mounts as single sub- assembly, but uses the same internal components as the original power supply.
High Pressure LED (BB)—Lights a red LED when the pressure is higher than the setpoint. Labels (BG)—Show which type of gas the Area Alarm Module is moni- • toring. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-15...
Page 29
NOTE: The MedPlus TotalAlert® Alarm Network Conversion Kit is shipped with a frame. The frame is surface-mounted to the dry wall around the existing rough-in box. Then, the front panel mounts to the frame.
The mounting brackets are not attached when they are shipped. Attach them prior to installation. For more information about installing an original alarm network, refer to the MedPlus TotalAlert® Alarm Network Installation Instructions. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Features Chapter 1: Introduction When installing the MedPlus TotalAlert® Alarm Network Conversion Kit, the Breakout P.C. Board and the power supply assembly mount in the existing alarm’s rough-in box. The conversion kit power supply mounts as single sub- assembly, but uses the same internal components as the original power supply.
Both parts of the Local Alarm are installed at the same time. The back box (AH) mounts to any flat surface, typically the wall in the source equipment room; and the front panel (AI) mounts to the back box. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-19...
Page 33
• Power supply wiring assembly (AO) • Fuse holder (AM) Figure 1-10. Local Alarm Components NOTE: The Local Alarm is not available as a MedPlus TotalAlert® Alarm Network Conversion Kit. Page 1-20 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Detailed Component Descriptions Chapter 1: Introduction Detailed Component Descriptions The MedPlus TotalAlert® Alarm Network can consist of the following: Master Alarm, Area Alarm, Local Alarm, Area Alarm Network Communications Board, and gas-specific transducers that include the appropriate DISS, gas-specific, demand valves.
Page 35
Alarm. For wiring diagrams, refer to the foldouts at the rear of this manual. If the Network Communications Board is installed in the Area Alarm, the Master Alarm can monitor the operation and condition of MedPlus TotalAlert® Area Alarm Modules. Area Alarm Modules and transducers are programmed at the factory with unique serial numbers and manufacturing dates.
Page 36
• The alarm sounds. • The configured alarm points scroll on the display. If the alarm message is a custom message, the word custom displays instead of the message. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-23...
30-Point Master Alarm and a Three Module Area Alarm or a 30-Point Master with Six Area Alarm Module Combination Alarm (see table 1-20 on page 1–49). Page 1-24 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 38
A Combination Alarm that has a 30-Point Master Alarm with three Area Alarm Modules cannot interface with a building automation system. The Area Alarm Modules use the same connector that would otherwise interface with the building automation system. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-25...
The information in this section is intended to be used by Information Systems personnel. The MedPlus TotalAlert® Alarm Network has the option of connecting to a facil- ity’s building automation system (BAS). The BAS accesses the 30 source alarm points and summary information in the Master Alarm using an N2 open protocol in the Metasys®...
Page 40
2. If there are three oxygen Area Alarm Modules and three vacuum Area Alarm Modules connected to the alarm network, ADI5 equals six. If there are no Area Alarm Modules connected to the alarm network, ADI5 equals zero. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-27...
Page 41
Detailed Component Descriptions Chapter 1: Introduction If you are planning to use the Metasys® Building Management System with the MedPlus TotalAlert® Alarm Network, download the file named TotalAlertv3.ddl from the www.beaconmedaes.com Web site. The following program is the TotalAlertv3.ddl program: ********************************************************************** * BeaconMedæs TotalAlert®...
The High and Low setpoints for the Area Alarm Modules are pre-set according to NFPA 99 standards (see table 1-4 on page 1–31). However, the set- points can be adjusted in the field. Page 1-30 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 44
Area Alarm Module sends the alarm message and reading to the Master Alarm. When an error occurs in the Area Alarm system, the error code displays, and the alarm sounds. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-31...
Page 45
“never.” Set the alarm to return every 30 minutes. A Test key starts a self-diagnostic routine. • The seven segment displays light each individual segment. • The LEDs light. • The audible alarm sounds. Page 1-32 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Table 1-6. Viewing Options Available for the Area Alarm by Using the Front Panel Option Description dFLt Sets alarm to default values 9ASt Gas type ScAL Measuring scale trEu Transducer firmware revision ArEu Area Alarm Module firmware revision MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-33...
Page 47
Log of events and alarms for this Area Alarm. Software version, device location, and device name Model identification used by the Information Systems personnel. Communication statistics used by Information Network statistics Systems personnel. Page 1-34 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 48
An additional label space is provided at the base of each module, for field use, to note the location that the module is monitoring. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-35...
The Area Alarm Blank Module reserves a space for future Area Alarm Modules to be added. Local Alarm The Local Alarm is a stand-alone component of the MedPlus TotalAlert® Alarm Network System. The Local Alarm provides connections for monitoring up to 16 signals from source equipment (see figure 1-13 on page 1–36).
When an alarm condition occurs, each Master Alarm can send electronic mes- sages to up to five users. In addition, the entire MedPlus TotalAlert® Alarm Network can be remotely monitored over the Internet. System Power Supply Each rough-in assembly or back box assembly for the original version of the MedPlus TotalAlert®...
Page 51
National Pipe Thread (NPT) female connection in the pipeline outside of the rough-in box assembly. Figure 1-14. Remote-Mount Transducers The remote-mount transducer can be used with either the original MedPlus TotalAlert® Alarm Network or the conversion kits. Page 1-38 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 52
The demand valve (DU) or adapter (DV) (when needed) attaches to a ¼" National Pipe Thread (NPT) female pipeline connector inside an existing rough-in box. If the adapter (DV) is needed, the demand valve (DU) attaches to the adapter (DV). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-39...
Page 53
Adapters are needed for the following gas types: vacuum, helium, nitrogen, waste anesthetic gas disposal (WAGD), carbon dioxide, and carbon dioxide/oxygen mixture. The local-mount transducer can only be used with the MedPlus TotalAlert® Alarm Network Conversion Kits (see table 1-16 on page 1–43). WARNING: Do not remove the threaded insert from the transducer.
Chapter 1: Introduction Specifications For MedPlus TotalAlert® Alarm Network specifications, refer to table 1-10 on page 1-41 through table 1-15 on page 1-42. Refer to table 1-16 on page 1-43 for the types of existing alarms that can be con- verted to a MedPlus TotalAlert®...
Page 55
50°F to 120°F (10°C to 49°C) Storage temperature - 40°F to 185°F (- 40°C to 85°C) Operating humidity 0% to 85% non-condensing Storage humidity 0% to 85% non-condensing FCC Part 15 Class A, emissions Page 1-42 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 56
Alarm 6819-A11 Integrated Alarm System I or Integrated 7½" x 9½" (190.5 mm Combination Alarm Alarm System II (30-point maximum x 241.3 mm) 6819-A13 master and a 3-gas maximum area) MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-43...
Page 57
Area Alarm (6-gas maximum) 228.6 mm) 6819-A11 Master Alarm plus Area Alarm (30- 14" x 9" (355.6 mm x Combination Alarm point maximum master and a 3-gas 228.6 mm) 6819-A13 maximum area) Page 1-44 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 58
16 3/16" x 16 11/16" (411 mm x 424 6819-A13 6819-A11 and 6819-A13 27 3/16" x 16 11/16" (691 mm x 424 mm) 2 3/8" (60.325 mm) extension from the All conversion kit alarm panels wall surface MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-45...
Specifications Chapter 1: Introduction Regulations, Standards, and Codes The MedPlus TotalAlert® Alarm Network meets the following regulations, stan- dards, and codes: Compressed Gas Association (CGA) G-4.1 (1996), Cleaning Equipment for Oxygen Service, Fourth Edition CGA C-9 (1988), Standard for Color Marking of Compressed Gas Cylinders...
Page 60
When configuring the alarm, do not set the alarm return time to “never.” Set the alarm to return every 30 minutes. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-47...
Black lettering, yellow background Nitrogen Black White lettering, black background Carbon dioxide Gray Black lettering, gray background Helium Brown White lettering, brown background Gray/green lettering, white back- Oxygen/Carbon dioxide mix White ground Page 1-48 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Model Identification Chapter 1: Introduction Model Identification There are several different configurations of the MedPlus TotalAlert® Alarm Network (6819), and the product numbers for each configuration are determined by the following factors (see table 1-20 on page 1–49): a. Revision level—All revisions are “A” at this time.
Page 63
6819-A13 # 30-Point Master Alarm Country Base code 6819-A1 ## 30-Point Master Alarm Conversion Kit Country Base code 6819-A9 ## 60-Point Master Alarm Country Base code 6819-A2 ## Page 1-50 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 64
Table 1-22. Transducer Codes to be Used when Ordering a Three-Module or Six-Module Conversion Kit (6819-A10 or 6819-A11) Code Letter Transducer type Local-mounted transducers (inside rough-in box) Remote-mounted transducers (on gas pipeline) MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-51...
Page 65
Table 1-24. Country Code Country Code Country United States Canada Table 1-25. Cover Plate Code Cover Plate Code Description 1-signal rough-in box cover plate 2-signal rough-in box cover plate Page 1-52 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 66
United States. Area Alarm Conversion kit with six modules: air, oxygen, vacuum, air, oxygen, vacuum for Canada. 6819-A110L-AOVAOV02 Transducers to mount inside the rough-in box (local-mount). Without communications option. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-53...
NFPA 99 standard or CSA Z305.1-92 code dictated by the authority having jurisdiction. Misconnection of med- ical gas or vacuum can result in serious or fatal injury to patients. Page 1-54 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Labels (provided) Input signal data table During the installation of the MedPlus TotalAlert® Alarm Network, a data table should have been completed for the source input signals that are connected to the Master Alarm (see table 1-27 on page 1–56).
Page 69
Master Alarm Labeling Chapter 1: Introduction Table 1-27. Master Alarm Signal Input Data Breakout Board Gas/Vacuum LED Number System Number Alarm Message Input Number Type (1 - 9) (1 - 9) Page 1-56 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 70
Reserve Pressure Low 2nd Supply in Use Reserve Supply in Use Reserve Supply Low a System Malfunction Service Required Custom Message a. Cylinder reserve less than (1) hour supply. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-57...
Page 71
1-27 on page 1–56). 5. Locate and remove the label strips (BY) from the openings (BZ). NOTE: More label strips are supplied with the Master Alarm, if needed. Page 1-58 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 72
10. For more information about installing an original alarm network, refer to the MedPlus TotalAlert® Alarm Network Installation Instructions. 11. For more information about installing a conversion kit alarm network, refer to the MedPlus TotalAlert® Alarm Network Conversion Kits Installation Instructions. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-59...
2. Turn the power switch (DC) to the ON position. The Master Alarm displays the following in two second intervals: Booting BeaconMedæs TotalAlert System Version: #.## SN: ##### Browse at http:// Master##### Page 1-60 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 74
The first LED (CW) indicates whether the software is operating correctly. – Steady flash indicates proper operation. – Solid ON or solid OFF indicates that the module has failed. – Rapid flashing indicates a software error. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-61...
Page 75
6. If the alarm has just been installed, or if any Area Alarm Modules communi- cating with the Master Alarm have been removed or replaced, do the Clear Network function (refer to step 7 on page 1-67). Page 1-62 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Using a 5/32" hex wrench, unlock the front panel (DM) (see figure 1-19 on page 1–63). b. Open the front panel (DM). c. Locate the Master Alarm Module (DN). Figure 1-19. Master Alarm MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-63...
Page 77
Immediately upon entering the configuration mode, the Master Alarm display scrolls the following: *** Device *** *** Setup *** BeaconMedæs TotalAlert System Press ‘Silence’ for the next item Press ‘Test’ to change the value Page 1-64 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
While in the configuration mode, the front panel keys operate differently than they do in normal operation mode (see figure 1-21 on page 1–65 and table 1-29 on page 1-66). Figure 1-21. Master Alarm Front Panel MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-65...
Page 79
“never.” Set the alarm to return every 30 minutes. The next option is for the N2 Address. This is the Ethernet network address for the optional connection to a building automation system. Page 1-66 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 80
Test key to scroll through the following choices: 8. Press the Silence key to select one. NOTE: If Yes is chosen, the device list clears, and the value immediately toggles back to MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-67...
Page 81
If you use the Web pages to configure the Master Alarm, you can customize mes- sages. When there are multiple systems for the same type of gas or vacuum, configuring a System number helps to identify the source. Page 1-68 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 82
18. Repeat step 9 through step 17 in order. The display advances to the next option, which is the Gas Type for the next consecutive input, until Input 30 is configured. NOTE: After Input 30 is configured, the alarm returns to normal operation. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-69...
Chapter 1: Introduction Glossary of Terms for Web Page Usage Before using the MedPlus TotalAlert® Alarm Network dynamic Web pages, you may need to know the following terms or expressions: Browsing a Web Page—Looking at information found on a Web page.
When the display reads Webbrowse@http://Master#####, that is the Master alarm’s name. 4. Type the word Master followed by its serial number (without a space) into your browser’s address window (CM) (see figure 1-22 on page 1–72). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-71...
Page 85
Alarm, you can still use the Device Name to get into the Master Alarm Home Page. After you enter the Device Name into your browser’s address window, the Master Alarm’s Home Page displays (see figure 1-23 on page 1–73). Page 1-72 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 86
Configuring and Browsing the Master Alarm Using the Web Pages Chapter 1: Introduction Figure 1-23. Master Alarm Home Page 5. Make selections for configuring and monitoring from the Home Page. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-73...
The computer stays logged in until the user closes the browser. 2. Click in the User Name window. 3. Type new in that window. 4. Click in the Password window. 5. Type new in that window. Page 1-74 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 88
Figure 1-25. User Administration 10. Click in the User 1 Name window under the User Name column. 11. Type in the name of the first user in that window. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-75...
Page 89
There does not have to be three administers. If you forget your password, call BeaconMedæs Technical Support at 1-888-4MEDGAS (1-888-463-3427); and ask for the Security Log-In Password for the MedPlus TotalAlert® Alarm Network. Page 1-76 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
3. Click on the number link in the Alarm Input column for the input that you want to configure. The Alarm Step 2 page displays (see figure 1-27 on page 1–78). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-77...
Page 91
Chapter 1: Introduction Figure 1-27. Alarm Step 2—Master Alarm Setup 4. Click on the Gas Type pull down menu arrow. The gas types menu displays (see figure 1-28 on page 1–79). Page 1-78 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 92
1–80). NOTE: If you want a custom message in the Gas Type window, click on Custom as the type of gas then type in the message you want displayed. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-79...
Page 93
7. To choose a front panel LED, click on the LED pull down menu arrow. The LED numbered list displays (see figure 1-30 on page 1–81). NOTE: When you are facing the front panel, the LEDs are numbered one through nine. Page 1-80 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 94
System number helps to identify the source. 9. To choose a system number, click on the System pull down menu arrow. The available system numbers display (see figure 1-31 on page 1–82). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-81...
Page 95
12. To create a custom message, click on the Message pull down menu arrow and choose Custom Message (see figure 1-32 on page 1–83). The Custom Message Setup screen displays (see figure 1-33 on page 1–83). Page 1-82 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 96
Chapter 1: Introduction Figure 1-32. Custom Message Screen Figure 1-33. Custom Message Setup 13. Click inside the Custom Message window, and type the message you want displayed when this error occurs. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-83...
Page 97
The Alarm Complete page displays (see figure 1-34 on page 1–84). Figure 1-34. Alarm Complete To return to the Alarm Message Setup page and to the next input, click on the Return to Alarm Messages link. Page 1-84 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Without the NetBios Name Service enabled, the device must be accessed by using its IP address. c. To learn the Master Alarm’s IP address, press the Test key on its front panel. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-85...
Page 99
5. Click on the location of this Master Alarm. 6. Click in the Zone window. 7. Type in the zone number of this Master Alarm. NOTE: Zones 1 through 9999 are available. Page 1-86 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 100
11. Click on the direction of the wing that this Master Alarm is located on. 12. Click on the Silenced return time pull down menu arrow (see figure 1-38 on page 1–88). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-87...
Page 101
This is an option. An RS-485 interface from the alarm to the facility’s building automation system can be used. If used, both the Master Alarm and the facility’s building automation system receive alarm signals. Page 1-88 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 102
20. When you are finished setting up this Master Alarm, click on the Submit but- ton. The Device Setup Accepted page displays (see figure 1-39 on page 1–89). Figure 1-39. Device Setup Accepted MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-89...
The SMTP Server Name requires a Domain Name Server (DNS) look-up. Alarms that occur before the server name is resolved are not sent. 4. If you know the SMTP Server Address, click in the SMTP Server Address window. Page 1-90 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 104
Submit button. The Electronic Notification Changes Accepted window dis- plays (see figure 1-41 on page 1–92). When you receive electronic mail from the MedPlus TotalAlert® Alarm Network, it has the user in the Email Address 1 position in the received mes- sage’s “From”...
Set Master Alarm’s Clock 1. To set the clock, click on the Set Clock link. The Set Clock page displays (see figure 1-42 on page 1–92). Figure 1-42. Set Clock Page 1-92 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 106
12. Click on the Second pull down menu arrow. 13. Click on the current second in that window. 14. When you are finished setting up the clock, click on the Submit button. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-93...
If you choose the Fixed IP address option, you must also use a fixed SMPT server address. 4. To learn more about the Internet assignments, see “Setting up the Internet Interface” on page 6-11. Page 1-94 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Network Communications Boards, or the Area Alarm Modules. Otherwise, alarms will occur when the network does not report as expected. 3. To clear the alarm network’s device list, click on the Click Here link. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-95...
The electronic notification recipients and the alarm network settings do not trans- fer. 1. To transfer the device configuration, click on the Transfer Setup link. The Configuration Transfer page displays (see figure 1-45 on page 1–97). Page 1-96 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 110
3. Click on the Master Alarm that you want the configuration to be transferred NOTE: The transfer function can only be done across the Ethernet. You cannot transfer the configuration by using the RS-232 serial port. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-97...
NOTE: When the Network Communications Board is installed in the Area Alarm, you can monitor all of the inputs on the MedPlus TotalAlert® Alarm Network. Otherwise, only the Master Alarms’ inputs are shown. 2. Click on the Refresh link to view the most recent information.
Figure 1-47. Event Log When the Network Communications Board is installed in the Area Alarm, the event log captures all alarms and events on the MedPlus TotalAlert® Alarm Network. Otherwise, it only captures events and alarms from the Master Alarms.
2. To configure another device on the alarm network use the jump link. 3. To browse information about another device on the alarm network use the view link. 4. Click on the Refresh link to view the most recent information. Page 1-100 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
The Device Information page displays (see figure 1-49 on page 1–101). Figure 1-49. Device Information This information is useful for the facility’s Information Systems personnel to determine software version, device location, and naming information. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-101...
3. To browse the alarm network statistics, choose Network Statistics (see “Browse Alarm Network Statistics” on page 1–104). 4. To browse the inputs, choose Physical Inputs (see “Browse Input States” on page 1–107). Page 1-102 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Click in the File Name window, and type the name you want to save the file as in that window. d. Click on the Save button. 3. To browse the configuration on the monitor, click on the Click Here link. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-103...
2. For a description of the alarm network statistics, refer to table 1-30 on page 1-105. 3. Click on the Refresh link to view the most recent information. Page 1-104 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 118
Not enough memory to build a MedPlus TotalAlert® packet. Peer ARP waiting Transmission is delayed until the ARP resolves the MAC address. Peer no send MedPlus TotalAlert® packet not sent, because there are no packet buffers. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-105...
Page 119
PMP missed end RS-485 packets that did not frame correctly. PMP too long RS-485 packets that exceeded the expected length. Area bus timeouts RS-485 requests that had no response. Page 1-106 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Diagnostics page displays (see figure 1-53 on page 1–107). Figure 1-53. Input Diagnostics NOTE: This page is useful when troubleshooting the alarm system’s wiring. 2. Click on the Refresh link to view the most recent information. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-107...
Front panel keys (see “Configuring the Area Alarm by Using the Front Panel” on page 1–115) • Web pages (see “Browsing the Area Alarm by Using the Web Pages” on page 1–122) Page 1-108 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Turn off the power supply in the alarm, and leave it off during the installa- tion of any component or sub-assembly. Failure to do so could result in personal injury or equipment damage. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-109...
Page 123
Click on the icon that looks like a printer. 9. Stick the appropriate Avery® labels to the front side of the label holder (CG). 10. Place the label holders (CG) back onto the mounting studs (CH). Page 1-110 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 124
15. For more information about installing an original alarm network, refer to the MedPlus TotalAlert® Alarm Network Installation Instructions. 16. For more information about installing a conversion kit alarm network, refer to the MedPlus TotalAlert® Alarm Network Conversion Kits Installation Instructions. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-111...
4. Determine whether the P.C. board is the Network Communications Board (DH) or Connector P.C. Board (not shown). NOTE: The Connector P.C. Board does not have LEDs on it. Page 1-112 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 126
The first LED (CZ) indicates whether the software is operating correctly. – Steady flash indicates proper operation. – Solid ON or solid OFF indicates that the module has failed. – Rapid flashing indicates a software error. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-113...
Page 127
Area Alarm Module has not been factory-programmed. Send it back to BeaconMedæs (see “Service Parts Ordering” on page 5–4). 6. If the Area Alarm is functioning properly, lock the front panel (DF). Page 1-114 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
The Connector P.C. Board does not have LEDs on it. 4. Press the configuration button (CE) or (CF), located on the P.C. board until 9ASt displays on the Area Alarm Module (see figure 1-58 on page 1–116). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-115...
Page 129
Configuring the Area Alarm by Using the Front Panel Chapter 1: Introduction Figure 1-58. Area Alarm Configuration Button Page 1-116 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 130
When the intended setting displays, release the Test key. NOTE: If nA displays, that option is not available. 5. You can return to normal operation and save the changes that you have made at any time. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-117...
Oxygen M7Ed Medical air UAcu Vacuum WJA9 WAGD (waste anesthetic gas disposal) nito Nitrous oxide nit9 Nitrogen cArb Carbon dioxide hELi Helium Oycd Oxygen and carbon dioxide mixture Page 1-118 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 132
WUES • is west. FLor 8. Configure . This is the floor level that the module is monitoring. You can choose from , which are sub-basement levels, through MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-119...
Page 133
SUrG • is surgery area. trAU • is trauma area. 2onE 10. Configure . This is the zone that the module is monitoring. It can be 9999 from through Page 1-120 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 134
13. View . This is the firmware revision for the transducer. ArEu 14. View . This is the firmware revision for the Area Alarm Module. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-121...
After you log into the Area Alarm, the Area Communications Module Home page displays (see figure 1-60 on page 1–122). Figure 1-60. Area Alarm Network Communications Board Home 3. Make viewing selections from the Area Communications Home page. Page 1-122 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Figure 1-61. Active Area Alarms 2. Use this page to monitor all of the Area Alarm Modules. 3. Click on the Refresh link to view the most recent information. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-123...
It also allows the facility’s engineering staff to keep track of all of the pres- sure readings from the transducers at the same time. 2. Click on the Refresh link to view the most recent information. Page 1-124 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
1-63 on page 1–125). Figure 1-63. Device Info—Area Alarm This information is useful for the facility’s Information Systems personnel to determine software version, device location, and naming information. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-125...
View Area window. The Masters page displays (see figure 1-64 on page 1–126). Figure 1-64. Masters—Masters on this Network 2. Use this page to learn which Master Alarms are communicating with this Network Communications Board. Page 1-126 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
The Area Alarm Event Log logs only Area Alarm events. The Master Alarm Event Log logs all MedPlus TotalAlert® Alarm Network events. The event log can be downloaded and saved to a file on a PC as part of a regular maintenance schedule.
1–128). Figure 1-66. Communications Statistics—Area Alarm This information is useful for the facility’s Information Systems personnel. 2. Click on the Refresh link to view the most recent information. Page 1-128 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
2. To aid in the labeling process, you may want to complete the following table. Table 1-32. Local Alarm Input Signal Data Input Number Input Source Alarm Message MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-129...
Page 143
7. Unplug the power supply wiring (CU). 8. Remove the front panel (CO). 9. For ease of handling while you are labeling; turn the front panel (CO) around and slide it onto the screws (CN). Page 1-130 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 144
The labels are for either the left-hand or right-hand side. 14. For more information about installing an original alarm network, refer to the MedPlus TotalAlert® Alarm Network Installation Instructions. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-131...
16 inputs. If there is an alarm condition upon power-up, the alarm sounds. 4. If the Local Alarm is functioning properly, secure the front panel (DJ) to the back box (DL). Page 1-132 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
TotalAlert® Alarm Network. Troubleshooting by unauthorized personnel could result in personal injury or equipment damage. WARNING: Only facility-authorized personnel should perform preventive maintenance on the MedPlus TotalAlert® Alarm Network. Preventive maintenance per- formed by unauthorized personnel could result in personal injury or equip- ment damage. WARNING: Follow the product manufacturer’s instructions.
Page 147
Master Alarms correctly could endanger patient welfare. WARNING: Change the factory-programmed password after the first time you log in. Otherwise, inappropriate personnel may change the setpoints and endan- ger patient welfare. Page 1-134 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 148
SHOCK HAZARD: The potential for electric shock exists with electrical equipment. Establish policies and procedures to educate your staff on the risks associated with electrical equipment. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-135...
Page 149
The potential for electric shock exists with electrical equipment. Use cau- tion when troubleshooting any electrical device. SHOCK HAZARD: Properly ground the MedPlus TotalAlert® Alarm Network Conversion Kit. Failure to do so could cause personal injury or equipment damage. SHOCK HAZARD: Use care when installing the high voltage cover.
Page 150
Equipment damage can occur. CAUTION: The Information Systems personnel should be notified before changing any of the network settings. Changing the settings could keep the equip- ment from working properly. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 1-137...
Page 151
The default command sets the Area Alarm Module back to the factory defaults. If you do not want the factory default values, choose no. Otherwise, the alarm may not operate as intended. Page 1-138 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 152
Otherwise, the MedPlus TotalAlert® Alarm Network will indicate that an error has occurred. CAUTION: When two or more MedPlus TotalAlert® Alarm Network systems are on the same Ethernet network but not separated by a router, the alarm will not operate as intended.
Page 156
Area Alarm Program Errors ..................2-18 Area Alarm Module RAM Error ................2-18 Area Alarm Module ROM Error ................2-19 Battery Low on Master Alarm..................2-19 Ethernet Connection Is Lost..................2-20 Area Display/Transducer Fault ................2-21 Service Required .....................2-22 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-1...
Using the Device Name Does Not ................2-41 While Browsing the Master Alarm, Area Alarm Modules Are Not Accessible ......................2-42 Text Message Is Not Received by Your Digital Telephone ........2-44 Page 2-2 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
To verify the repair, perform the Final Actions after the Function Checks. If the troubleshooting procedures do not isolate the problem, call BeaconMedæs Technical Support at 1-888-4MEDGAS (1-888-463-3427) for assistance. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-3...
Go to “Function Checks” on page 2-5. 3. The problem is a result of improper operator action. Go to “Function Checks” on page 2-5. 4. To ensure proper operation of the MedPlus TotalAlert® Alarm Network, per- form the “Function Checks” on page 2-5. Page 2-4...
6. LEDs 1 through 9 individually light red. 7. Audible Test displays. 8. The alarm sounds for 2 seconds. 9. The flash memory checksum and the Master Alarm’s Internet Protocol (IP) address displays. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-5...
The Local Alarm has a self-test for the LEDs and audible alarm. The self-test is activated by pressing and holding the Test key for two seconds. The red LEDs light, and the alarm sounds. Page 2-6 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
2. Return all equipment to normal operating condition. a. Connect any disconnected wires and connectors. b. Close all panels. c. Remove all tools and test equipment. 3. Complete all required administrative tasks. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-7...
Area Alarm The error codes for the Area Alarm Modules are used to help identify and solve problems with the facility’s gas system or the MedPlus TotalAlert® Alarm Network (see table 2-1 on page 2-8). Table 2-1. Area Alarm Module Error Codes...
The factory-programmed alarm messages for the Master Alarm are used to help identify and solve the problems that may occur with the facility’s gas system or the MedPlus TotalAlert® Alarm Network. There are certain messages available depending on the type of gas (see table 2-3 on page 2-10).
Page 165
If using an Ethernet connection, refer to “Setting up the Internet Interface” on page 6-11, otherwise refer to “NULL Modem Driver Setup Instructions for Windows® Operating System” on page 6-20. Page 2-10 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
No action is required. properly. Rapid flash Device error. Replace the transducer. LED off No power to the transducer, Connect the power, or or the transducer has failed. replace the MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-11...
Replace the transducer (refer to procedure 4.23 on page 4-62). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 5. 5. If the problem still exists, call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-13...
Replace the transducer (refer to procedure 4.23 on page 4-62). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 4. 4. If the problem still exists, call BeaconMedæs Technical Support. Page 2-14 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Connect the transducer properly (refer to procedure 4.23 on page 4-62). If you need more information about how to connect a transducer, refer to the MedPlus TotalAlert® Alarm Network— Conversion Kits Installation Instructions. If this solves the prob- lem, go to “Final Actions” on page 2-7. Otherwise, go to step 3.
Connect the proper gas-specific transducer (refer to procedure 4.23 on page 4-62). If you need more information about how to connect the transducer, refer to the MedPlus TotalAlert® Alarm Network—Conversion Kits Installation Instructions . If this solves the problem, go to “Final Actions” on page 2-7.
Replace the transducer wiring (refer to procedure 4.20 on page 4-50). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 5. 5. If the problem still exists, call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-17...
Replace the Area Alarm Module (refer to procedure 4.9 on page 4-26). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 4. 4. If the problem still exists, call BeaconMedæs Technical Support. Page 2-18 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
4-12). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 3. 3. If the problem still exists, call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-19...
Call the facility’s Information Systems department. If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 6. 6. If the problem still exists, call BeaconMedæs Technical Support. Page 2-20 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Replace the transducer (refer to procedure 4.20 on page 4-50). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 6. 6. If the problem still exists, call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-21...
(refer to procedure 4.9 on page 4-26). This solves the problem. Call BeaconMedæs Technical Support. 4. Go to “Final Actions” on page 2-7. Page 2-22 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
(refer to procedure 4.9 on page 4-26 and procedure 4.23 on page 4-62). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 3. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-23...
5. Check the LEDs on the Network Communications Board (see “Area Alarm Power-Up” on page 1–112). The LEDs that indicate whether the alarm is communicating are operating correctly. Call BeaconMedæs Technical Support. Page 2-24 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Master Alarm by Using the Front Panel” on page 1-63, or “Clear Alarm Network Device List” on page 1-95. This solves the problem. Call BeaconMedæs Technical Support. 4. Go to “Final Actions” on page 2-7. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-25...
Master Alarm by Using the Front Panel” on page 1-63, or “Clear Alarm Network Device List” on page 1-95. This solves the problem. Call BeaconMedæs Technical Support. 4. Go to “Final Actions” on page 2-7. Page 2-26 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Replace the Network Communications Board. If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, call BeaconMedæs Technical Support. 5. Call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-27...
4. Replace the Area Alarm Module (refer to procedure 4.9 on page 4-26). This solves the problem. Call BeaconMedæs Technical Support. 5. Go to “Final Actions” on page 2-7. Page 2-28 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Turn the power to the device on. If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 4. 4. Call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-29...
Connect the two orange leads from the power supply to the breakout board (refer to procedure 4.7 on page 4-22). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 5. Page 2-30 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 186
Replace the transformer (refer to procedure 4.5 on page 4-16). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, call BeaconMedæs Technical Support. 8. Go to “Final Actions” on page 2-7. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-31...
Connect the two orange leads from the power supply to the breakout board (refer to procedure 4.4 on page 4-14). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 5. Page 2-32 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 188
Replace the transformer (refer to procedure 4.5 on page 4-16). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, call BeaconMedæs Technical Support. 8. Go to “Final Actions” on page 2-7. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-33...
5. The facility’s supply voltage is connected to the alarm’s terminal block. Connect the facility’s supply to the alarm’s terminal block. For the wiring diagram, refer to FO 3-1 at the rear of this document. Page 2-34 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 190
Replace the transformer (refer to procedure 4.13 on page 4-36). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, call BeaconMedæs Technical Support. 8. Go to “Final Actions” on page 2-7. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-35...
4-26) on the alarm panel that will not silence. If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, call BeaconMedæs Technical Support. 2. Go to “Final Actions” on page 2-7. Page 2-36 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
(refer to procedure 4.8 on page 4-24). If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, call BeaconMedæs Technical Support. Go to “Final Actions” on page 2-7. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-37...
Using the Front Panel” on page 1-63. If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, call BeaconMedæs Technical Support. 3. Call BeaconMedæs Technical Support. Page 2-38 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Master Alarm Module. See “Master Alarm Power-Up” on page 1-60. The LED is flashing at a steady rate. Call BeaconMedæs Technical Support. 5. If you still cannot browse the Master Alarm, call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-39...
Information Systems personnel will have to eliminate some of the traffic flow, by fixing their other equipment. The browsing works correctly after the Information Systems personnel fix their other equipment. Call BeaconMedæs Technical Support. Page 2-40 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Install “Client for Microsoft® Networks.” If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 4. 4. If the problem still exists, call BeaconMedæs Technical Support. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-41...
Call your facility’s Information Systems personnel to fix the problem. If they fix the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 5. 5. If the problem still exists, call BeaconMedæs Technical Support. Page 2-42 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 198
While Browsing the Master Alarm, Area Alarm Modules Are Not Accessible Chapter 2: Troubleshooting Procedures NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-43...
Type in the correct address for the telephone. Refer to “Configure Electronic Notification” on page 1-90. If this solves the problem, go to “Final Actions” on page 2-7. Otherwise, go to step 6. Page 2-44 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 200
After the service provider has fixed their problem, try to page the digital telephone again. The problem is solved. Call BeaconMedæs Technical Support. 11. Go to “Final Actions” on page 2-7. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 2-45...
Page 201
Text Message Is Not Received by Your Digital Telephone Chapter 2: Troubleshooting Procedures NOTES: Page 2-46 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 202
Master Alarm Wiring Conventions ..............3-8 Output Relays on Master Alarms ..............3-10 Local Alarm Wiring Conventions...............3-11 Area Alarm Wiring Conventions................3-13 Output Relay on Area Alarms ..............3-14 Ethernet Wiring Conventions ................3-14 Wiring Diagrams ......................3-15 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 3-1...
Chapter 3: Theory of Operation Theory of Operation The MedPlus TotalAlert® Alarm Network is a fully electronic monitoring sys- tem. It monitors and displays the status of all piped gas and vacuum systems that are in a typical healthcare facility by using Master Alarms, Area Alarms, and Local Alarms that monitor the following: •...
Page 205
During an alarm condition or a system error on the Master Alarm, the following occurs: • Master Alarm sounds an alarm, and the corresponding red alarm LED lights, if applicable (errors do not light LEDs). • Message displays. Page 3-4 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 206
• Alarm silence key to silence the audible alarm. • Red LEDs that remain lit until the alarm condition is no longer present. • Test key to perform a self-test of each alarm. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 3-5...
MedPlus TotalAlert® Alarm Network (see figure 3-1 on page 3–7). When the installation of the MedPlus TotalAlert® Alarm Network is done prop- erly, the wiring complies with National Electrical Code® (NEC®) requirements and the following general requirements: •...
Page 208
Medical Gas Network System Interaction Chapter 3: Theory of Operation Figure 3-1. Block Diagram of a Typical MedPlus TotalAlert® Alarm Network MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 3-7...
(+) terminal and the common contact wire to the negative (-) termi- nal. • Switches sensing both high pressure and low pressure have independently operating sets of contacts, one set for low pressure and one for high pressure. Page 3-8 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 210
For the low pressure sensor, maintain polarity by wiring the normally open contact wire to the positive (+) terminal and the common contact wire to the negative (-) terminal. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 3-9...
When the Master Alarm condition is remedied, this relay deactivates. The Master Alarm also has an output relay that can be used to interface with a building automation system. Page 3-10 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Master Alarms. The Local Alarm has individual signals connected to each alarm input. • Polarity is determined by the indicators on the MedPlus TotalAlert® Alarm Network Local Alarm. Switches and contacts are not usually marked with polarity indicators.
Page 213
Local Alarm Wiring Conventions Chapter 3: Theory of Operation Figure 3-3. Typical Local Alarm Wiring Conventions Page 3-12 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
The other two wires may be connected in either the “A” and “B” posi- tions (see figure 3-4 on page 3–13). • When installing a MedPlus TotalAlert® Alarm Network Area Alarm, the pro- vided gas-specific transducers must be used for proper alarm operation.
Ethernet network, refer to the MedPlus TotalAlert® Alarm Network— Information System Requirements Technical Data Sheet. Some of the requirements when using the Ethernet with the MedPlus TotalAlert® Alarm Network are as follows: • The Master Alarms, Area Alarms, and any personal computers (PCs) used in the alarm network must be connected to a common Ethernet system.
A Master Alarm with three Area Alarm Modules is also available. It is similar to the wiring diagram of the Master Alarm with six Area Alarm Modules; however, it does not have an RS-485 connection to interface with a building automation system. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 3-15...
Page 217
Wiring Diagrams Chapter 3: Theory of Operation NOTES: Page 3-16 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 218
Master Alarm or Area Alarm Transformer ...............4-16 Removal......................4-16 Replacement .......................4-17 Master Alarm or Area Alarm Conversion Kit Power Supply ........4-18 Removal......................4-18 Replacement .......................4-20 Area Alarm Breakout P.C. Board ................4-22 Removal......................4-22 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-1...
Page 219
Local Alarm Buzzer Assembly.................4-38 Removal......................4-38 Replacement .......................4-39 Power Supply Fuse....................4-40 Removal......................4-40 Replacement .......................4-41 Power Supply Fuse Holder..................4-42 Removal......................4-42 Replacement .......................4-43 Power Switch......................4-44 Removal......................4-44 Replacement .......................4-45 Adjustable Grip Latch ....................4-46 Page 4-2 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Also, to avoid damaging the unit or any of its components, no maintenance or testing should be undertaken by qualified individuals who are not completely familiar with the procedures in this manual. Personal injury or equipment damage could occur. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-5...
4. Unlock the front panel (A) (see figure 4-1 on page 4–7) or (see figure 4-2 on page 4–8): • If removing a front panel from an original MedPlus TotalAlert® Alarm Network, see figure 4-1 on page 4–7. • If removing a front panel from a MedPlus TotalAlert® Alarm Network Conversion Kit, see figure 4-2 on page 4–8.
Page 224
Master Alarm and Area Alarm Front Panels (not Including Area Alarm Modules) Chapter 4: Removal, Replacement, and Adjustment Procedures Figure 4-1. Master Alarm and Area Alarm Front Panels MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-7...
Page 225
Master Alarm and Area Alarm Front Panels (not Including Area Alarm Modules) Chapter 4: Removal, Replacement, and Adjustment Procedures Figure 4-2. Master Alarm and Area Alarm Front Panels on Conversion Kits Page 4-8 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Chapter 4: Removal, Replacement, and Adjustment Procedures Replacement 1. To replace the front panel, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-9...
3. Push open the ears (D) of the connectors to remove the ribbon cables (B). 4. Using a screwdriver, remove the four screws (C) that secure the Master Alarm Module (E) to the front panel (A). Page 4-10 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
6. Remove the Master Alarm Module (E). Replacement 1. To replace the Master Alarm Module, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-11...
2. Turn the power switch (D) to the OFF position. 3. Slide a screwdriver underneath the battery (C), and lift it out of its holder (B). Page 4-12 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Chapter 4: Removal, Replacement, and Adjustment Procedures Replacement 1. To replace the battery, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-13...
2. Turn the power switch (G) to the OFF position. 3. Note the positions of the wiring at the connectors (I) for the source equip- ment. 4. Using a screwdriver, loosen the screws in the connectors (I). Page 4-14 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Alarms, otherwise they may not operate as intended. 1. To replace the Breakout P.C. Board, reverse the order of the removal instruc- tions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-15...
3. Using a phillips head screwdriver, remove the five screws (A) that secure the cover plates (B) and (C) to the rough-in assembly (D) (see figure 4-6 on page 4–17). Page 4-16 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
1. To replace the transformer, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-17...
8. Remove the two screws (H) securing the power supply assembly (C) to the rough-in box (I). 9. Remove the high voltage cover (B) and the power supply assembly (C) from the rough-in box (I). Page 4-18 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 236
Master Alarm or Area Alarm Conversion Kit Power Supply Chapter 4: Removal, Replacement, and Adjustment Procedures Figure 4-7. Master Alarm or Area Alarm Conversion Kit Power Supply MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-19...
(D). Shock Hazard: Properly ground the MedPlus TotalAlert® Alarm Network Conversion Kit. Failure to do so could cause personal injury or equipment damage. 6. Connect the input power wires (G) to the terminal block (F) in the following order: line voltage to L, neutral to N, and ground to the earth ground symbol (K).
Page 238
Master Alarm or Area Alarm Conversion Kit Power Supply Chapter 4: Removal, Replacement, and Adjustment Procedures NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-21...
3. Push open the ears of the connectors (E) to remove the ribbon cable (B). 4. Note the positions of the wiring on the connector (I) for the transducers. Page 4-22 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
8. Pull the Breakout P.C. Board (C) off of the mounting pegs (D). Replacement 1. To replace the Breakout P.C. Board, reverse the order of the removal instruc- tions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-23...
2. Turn the power switch (H) to the OFF position. The Area Alarm has either a Connector P.C. Board (D) or a Network Communications Board (E) mounted to the back of the front panel (A). Page 4-24 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
5. Pull the P.C. board off of the mounting pegs (G). Replacement 1. To replace the P.C. board, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-25...
Area Alarm Modules; use the Clear Network function before you begin this procedure (see “Clear Alarm Network Device List” on page 1–95). Otherwise the MedPlus TotalAlert® Alarm Network displays the error “Connection Lost with Device…,” because it is searching for the replaced module instead of the new one.
Page 244
7. Press the retaining clips (H), and pull the retainer ring (I) off of the Area Alarm Module (F). 8. Remove the Area Alarm Module (F) and the retainer ring assembly (D and I). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-27...
Chapter 4: Removal, Replacement, and Adjustment Procedures Replacement 1. To replace the Area Alarm Module, reverse the order of the removal instruc- tions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. Page 4-28 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 246
Area Alarm Module Chapter 4: Removal, Replacement, and Adjustment Procedures NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-29...
2. Turn the power switch (D) to the OFF position. 3. Using a phillips head screwdriver, remove the two screws (B) from the Area Alarm blank module (C). Page 4-30 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Chapter 4: Removal, Replacement, and Adjustment Procedures Replacement 1. To replace the Area Alarm blank module, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-31...
3. Turn the power switch (F) to the OFF position. 4. Unplug the buzzer wiring (D). 5. Unplug the power supply wiring (C). Page 4-32 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
8. Remove the front panel (B). Replacement 1. To replace the front panel, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-33...
Failure to do so could result in personal injury or equipment damage. 3. Turn the power switch (H) to the OFF position. 4. Unplug the buzzer wiring (E). Page 4-34 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
10. Remove the P.C. board (C). Replacement 1. To replace the P.C. board, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-35...
(B) to slide off (see figure 4-14 on page 4–36). Figure 4-14. Local Alarm Transformer 3. Slide the front panel (B) up and off of the back box (C). 4. Unplug the buzzer wiring (D). Page 4-36 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
1. To replace the transformer, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-37...
Failure to do so could result in personal injury or equipment damage. 3. Turn the power switch (H) to the OFF position. 4. Unplug the buzzer wiring (C). 5. Unplug the power supply wiring (F). Page 4-38 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
9. Remove the buzzer assembly (D) and (E). Replacement 1. To replace the buzzer assembly, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-39...
5/32" hex wrench to unlock the front panel (A) (see figure 4-16 on page 4–40). • When changing the power supply fuse in the Local Alarm, use a phillips head screwdriver to remove the front panel. Figure 4-16. Power Supply Fuse Page 4-40 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
1. Ensure the replacement fuse is the same type and rating as the original fuse. 2. To replace the fuse, reverse the order of the removal instructions. 3. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-41...
5/32" hex wrench to unlock the front panel (A) (see figure 4-17 on page 4–43). • When changing the power supply fuse holder in the Local Alarm, use a phillips head screwdriver to remove the front panel. Page 4-42 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
(D) and the fuse (C), and save them for the replacement procedure. Replacement 1. To replace the power supply fuse holder, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-43...
5/32" hex wrench to unlock the front panel (A) (see figure 4-18 on page 4–45). • When changing the power supply fuse holder in the Local Alarm, use a phillips head screwdriver to remove the front panel. Page 4-44 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
6. Remove the power switch (F). Replacement 1. To replace the power switch, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-45...
2. Turn the power switch (G) to the OFF position. 3. Grasp and hold the latch (B). 4. Using a 5/32" hex wrench, turn the lock (A) counterclockwise to back the latch (B) down. Page 4-46 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
5. Close the front panel (F). 6. Using a 5/32" hex wrench, rotate the lock (A) clockwise until it no longer turns. 7. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-47...
2. Turn the power switch (D) to the OFF position. 3. Push open the ears (B) of the connectors holding the ribbon cable (C) that you want to remove. 4. Remove the ribbon cable (C). Page 4-48 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Chapter 4: Removal, Replacement, and Adjustment Procedures Replacement 1. To replace the ribbon cable, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-49...
2. Leave the threaded insert (A) in the transducer (B). The transducer is not a serviceable item (see figure 4-21 on page 4–51). 3. Using an adjustable wrench, remove the demand flow valve (C) from the tee port (D). Page 4-50 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 268
6. Using a small screwdriver, loosen the screws (H) that secure the three wires (G and I) to the terminal block (J). 7. Remove the wires (G and I) from the terminal block (J). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-51...
12. Check for leaks in the gas connections. 13. If there are leaks, repeat step 2 through step 11. 14. To ensure proper operation, perform the “Function Checks” on page 2–5. Page 4-52 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 270
Remote-Mount Transducer and Demand Flow Valve Assembly Chapter 4: Removal, Replacement, and Adjustment Procedures NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-53...
The illustration used in this procedure shows the rough-in components mounted in a three-gas rough-in box from Chemetron® as an example. 4. Note the position of the green wire (or shield wire) (A) (see figure 4-22 on page 4–55). Page 4-54 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
1. Ensure that the new gas-specific transducer (E) and DISS demand flow valve (F) are the correct gas or vacuum type. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-55...
Page 273
12. If there are gas leaks, repeat step 2 through step 6 until no gas leaks occur. 13. To ensure proper operation, perform the “Function Checks” on page 2–5. Page 4-56 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 274
Local-Mount Transducer and DISS Demand Flow Valve Assembly for Conversion Kits (excluding the conversion kit housed in an Area Line Pressure Alarm (0321) rough-in box) Chapter 4: Removal, Replacement, and Adjustment Procedures NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-57...
(C), remove the power supply assem- bly (C) by performing the following steps: a. Disconnect the two flag terminals (D) supplying power to the Area Alarm Breakout P.C. Board (E). Page 4-58 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 276
7. Remove the wires (L and O) from the terminal block (M). 8. Disconnect the DISS nut (P) from the DISS demand flow valve (B). 9. Remove the transducer (A). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-59...
9. Tighten the screws (N) securing the wires (L and O) to the terminal block (M). 10. If the power supply assembly (C) did not need to be removed, go to step 11. Otherwise, do the following: Page 4-60 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 278
13. If there are gas leaks, repeat step 2 through step 6 until no gas leaks occur. 14. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-61...
(see figure 4-24 on page 4–62). 2. Using an adjustable wrench, remove the DISS nut (A) from the DISS demand valve (I). Figure 4-24. Remote-Mount Transducer Assembly Page 4-62 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
3. Tighten DISS fittings until you feel resistance. They only need to be finger tight. 4. Check for gas leaks, and repair if necessary. 5. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-63...
(B), remove the power supply assembly (B) by performing the following steps: a. Disconnect the two flag terminals (C) supplying power to the Area Alarm Breakout P.C. Board (D). Page 4-64 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 282
6. Loosen the screws (M) securing the three wires (K and N) to the terminal block (L). 7. Remove the wires (K and N) from the terminal block (L). 8. Disconnect the DISS nut (O) from the DISS demand flow valve (P). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-65...
10. If there are gas leaks, repeat step 2 and step 3 until no gas leaks occur. 11. To ensure proper operation, perform the “Function Checks” on page 2–5. Page 4-66 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
2. Turn the power switch (D) to the OFF position. 3. Depending on the alarm, unplug the Ethernet cable from the Master Alarm Module (B) or from the Area Alarm Network Communications Board (C). Page 4-68 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Chapter 4: Removal, Replacement, and Adjustment Procedures Replacement 1. To replace the Ethernet cable, reverse the order of the removal instructions. 2. To ensure proper operation, perform the “Function Checks” on page 2–5. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 4-69...
Page 287
Internet Connections Chapter 4: Removal, Replacement, and Adjustment Procedures NOTES: Page 4-70 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 288
30-Point Master Alarm with Three Area Alarm Modules Conversion Kit ....5-32 Area Alarm Modules ....................5-36 Area Alarm Module Blank ..................5-38 Remote-Mount Transducer..................5-40 Local-Mount Transducer (Inside the Rough-In Box) ..........5-42 Connecting Cables....................5-44 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-1...
Page 289
Chapter 5: Parts List NOTES: Page 5-2 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
(including but not limited to temperature, pressure, humidity, or ventilation), improperly MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-3...
Master Alarm with six Area Alarm Modules is also different than the 0.5 A rough-in assemblies (see figure 5-4 on page 5-5). Figure 5-1. Front Panel Identification Label for Single Power Supply Models Page 5-4 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 292
Figure 5-2. Rough-In Identification Label for Single Power Supply Models Figure 5-3. Front Panel Identification Label for Dual Power Supply Models Figure 5-4. Rough-in Identification Label for Dual Power Supply Models Call BeaconMedæs Technical Support at 1-888-4MEDGAS (1-888-463-3427). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-5...
Page 293
Service Parts Ordering Chapter 5: Parts List NOTES: Page 5-6 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
MedPlus TotalAlert® Alarm Network. c. BeaconMedæs recommends having one transducer on hand for each type of gas that is being moni- tored by the MedPlus TotalAlert® Alarm Network. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-7...
Local Alarm Chapter 5: Parts List Local Alarm Figure 5-5. Local Alarm Page 5-8 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Area Alarm Chapter 5: Parts List Area Alarm Figure 5-7. Area Alarm Page 5-12 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 300
As required Area module retainers 205675 205361 Adjustable grip latch Area communications board 205502 Area connector board 205504 205292WW 1 Hinge, weldment, small 15250 Locknut washer base 205281 Backbox mounting bracket, small MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-13...
Page 301
Each alarm has either a connector P.C. board or a Network Communications Board. One ten-conductor ribbon cable assembly and one area module retainer are used for each Area Alarm Module. Page 5-14 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 302
Area Alarm Chapter 5: Parts List NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-15...
30-Point Master with Three Area Alarm Modules Chapter 5: Parts List 30-Point Master Alarm with Three Area Alarm Modules Figure 5-8. 30-Point Master Alarm with Three Area Alarm Modules Page 5-16 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 305
Azote (nitrogen), gas-specific area module (French) 205997 Flat cable snap-its 205503 Area breakout board One ten-conductor ribbon cable assembly and one area module retainer are used for each Area Alarm Module. Page 5-18 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 306
30-Point Master Alarm with Three Area Alarm Modules Chapter 5: Parts List NOTES MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-19...
30-Point Master Alarm with Six Area Alarm Modules Chapter 5: Parts List 30-Point Master Alarm with Six Area Alarm Modules Figure 5-9. 30-Point Master Alarm with Six Area Alarm Modules Page 5-20 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 308
As required Medical air, gas-specific area module (USA) 205684V As required Vacuum, gas-specific area module (USA) 205684N As required Nitrogen, gas-specific area module (USA) 205684X As required Nitrous oxide, gas-specific area module (USA) MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-21...
Page 309
Each alarm has either a Connector P.C. Board (205504) or a Network Communications Board (205502). One ten-conductor ribbon cable assembly and one area module retainer are used for each Area Alarm Module. Page 5-22 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 310
30-Point Master Alarm with Six Area Alarm Modules Chapter 5: Parts List NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-23...
Area Alarm Conversion Kit Chapter 5: Parts List Area Alarm Conversion Kit Figure 5-12. Area Alarm Conversion Kit Page 5-28 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 316
Ribbon cable assembly, 10 conductor, 10" 205675 As required Area module retainer 15250 Locknut washer base 205310 Label holder 205502 Area communications board 205504 Area connector board 205320 4 or 8 Screw MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-29...
Page 317
Each alarm has either a Connector P.C. Board or a Network Communications Board. One ten-conductor ribbon cable assembly and one area module retainer are used for each Area Alarm Module. Page 5-30 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 318
Area Alarm Conversion Kit Chapter 5: Parts List NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-31...
30-Point Master Alarm with Three Area Alarm Modules Conversion Kit Chapter 5: Parts List 30-Point Master Alarm with Three Area Alarm Modules Conversion Kit Figure 5-13. 30-Point Master Alarm with Three Area Alarm Modules Conversion Kit Page 5-32 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 320
206293 8 or 12 Nylon anchor 206197WW Extension cover plate (option for larger rough-in boxes) 55138 8 or 12 Screw 206198WW Transducer cover plate (option for larger rough-in boxes) MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-33...
Page 321
205997 Flat cable snap-it 55407 Sleeving, 15" (381 mm) long 5255503 Screw One ten-conductor ribbon cable assembly and one area module retainer are used for each Area Alarm Module. Page 5-34 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 322
30-Point Master Alarm with Three Area Alarm Modules Conversion Kit Chapter 5: Parts List NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-35...
Area Alarm Modules Chapter 5: Parts List Area Alarm Modules Figure 5-14. Area Alarm Modules Page 5-36 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 324
(French) 205684S As required Succion (vacuum), gas-specific area module (French) 205684U As required Azote (nitrogen), gas-specific area module (French) 205518 Ribbon cable assembly, 10 conductor, 10" MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-37...
Chapter 5: Parts List Area Alarm Module Blank Figure 5-15. Area Alarm Module Blank Table 5-13. Area Alarm Module Blank Item Number Part Number Quantity Description 205760 As required Area module blank Page 5-38 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 326
Area Alarm Module Blank Chapter 5: Parts List NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 5-39...
Page 332
System ........................6-20 Dial-Up Configuration ..................6-21 Serial Port (PPP) Connection ................6-22 Master Alarm Module or Network Communications Board Connection......................6-23 Multiple MedPlus TotalAlert® Alarm Network Systems in the Same Facility ........................6-24 General Information ....................6-25 Repair ........................6-25 Test........................6-27 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Message destinations are examined and passed only to the correct device. 10BaseT can connect at optimum speed. Switches improve network per- formance. Fire-wall—A computer or computer software that prevents unauthorized access to private data from outside computer users. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-3...
Page 335
Web Page—Page of information obtained from a computer network. Wide Area Network (WAN)—The Internet. Window—Divided areas on a PC display that are broken down into different types of information. Page 6-4 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 336
Glossary Chapter 6: General Procedures NOTES: MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-5...
Chapter 6: General Procedures Internet Quick-Start In a typical installation where the MedPlus TotalAlert® Alarm Network is con- nected to an existing network that already includes a computer system (E), net- work server (G), and in some cases a network router (H), do the following (see figure 6-1 on page 6–7):...
Page 338
Internet Quick-Start Chapter 6: General Procedures Figure 6-1. Managed Networks MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-7...
Page 339
NetBios Name Service enabled, the device must be accessed by its IP address. To learn the Master Alarm’s IP address, press the Test Key. Figure 6-2. Typical Internet Home Page The MedPlus TotalAlert® Alarm Network Home page displays (see figure 6-3 on page 6–9). Page 6-8...
Page 340
5. To browse the other devices on the alarm network, click on the Network Devices link. This page provides links to the other Master Alarms and Area Alarm Network Communications Boards (see figure 6-4 on page 6–10). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-9...
Page 341
Internet Quick-Start Chapter 6: General Procedures Figure 6-4. Network Devices Page Page 6-10 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Ethernet communication on most networks by using either an RS-232 serial connector (BP) or an RG-45 connector (BO) (see figure 6-5 on page 6–12). The devices communicate by using TCP/IP on most office networks. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-11...
Page 343
If using an Ethernet connection, you need the following: • PC with an Ethernet connection • PC with an Internet browser, such as Microsoft Internet® Explorer® • Ethernet cable with RG-45 connectors on each end Page 6-12 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Addressing on a Managed Network If connected to a managed network, the MedPlus TotalAlert® Alarm Network starts communicating automatically. Upon power-up, the alarm may behave as follows: 1.
Page 345
1. Start an Internet browser, such as Microsoft Internet Explorer® 4 or Netscape Navigator® 4, from a computer that is on the existing network (see figure 6-7 on page 6–15). Page 6-14 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Page 346
NetBios Name Service enabled, the device must be accessed by its IP address. To learn the Master Alarm’s IP address, press the Test key located on the front panel. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-15...
Page 347
4. Log in using your User Name and your Password. 5. After you are logged into the Master Alarm, click on the Setup Network link, the Network Setup page displays (see figure 6-9 on page 6–17). Page 6-16 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Browsers locate devices in the following three ways: 1. IP address Example: http://10.12.13.14 This method works; however, a device\qs IP address is often not known. 2. Local name lookup Example: http://Master400187 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-17...
Page 349
The Microsoft® 2000 Server has a dynamic DNS that enrolls devices automatically if the feature is enabled. If IS personnel allow access though the facility’s fire-wall, the device can be accessed from the Internet. Page 6-18 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Driver Setup Instructions for Windows® Operating System” on page 6–20). Addressing MedPlus TotalAlert® Alarm Network devices always use IP address 192.168.1.1 with a serial port connection. All of the Web pages that are accessible using the Ethernet are accessible using the serial port. However, the loading rate is much slower.
13. Select Generic NULL Modem from the list. 14. Select the serial port on your computer that you want to use. 15. Click on Next. 16. Click on Finish. Page 6-20 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Go to Communications. d. Click on Dial-Up Networking. 21. Edit the properties of the Dial-Up Connection by doing the following: a. Right click on the NULL Modem, and select Properties. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-21...
1. Double click on the dial-up connection. 2. Click on Connect. NOTE: No Password is required. 3. When two little monitors are on the task bar, the connection is established; click Close. Page 6-22 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
The Home page of the controller displays. 5. To close the session, do the following: a. Right click on the two little monitors on the task bar. b. Select Disconnect. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-23...
Ethernet network but not separated by a router, the alarm will not operate as intended. When two or more MedPlus TotalAlert® Alarm Networks are on the same Ethernet system but different IP sub-nets that are not separated by a router, all Master Alarms display “Lost”...
General Information Chapter 6: General Procedures General Information Repair, test, and maintenance protocols for the MedPlus TotalAlert® Alarm Network are in the following sections. Repair Do not use a unit that is not functioning properly until all necessary repairs have been made.
Page 357
BeaconMedæs Technical Support at 1-888-4MEDGAS (1-888-463-3427). Except where BeaconMedæs warranty is applicable, repairs will be made at the current list price for the replacement part(s) plus the current hourly labor charge. Page 6-26 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
NFPA 99 stan- dard. Calibration All calibration is performed at the factory. If a unit fails or gives erratic readings, contact BeaconMedæs Technical Support at 1-888-4MEDGAS (1-888-463-3427). MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-27...
(For customers in the US, the disinfectant should be registered with the Environmental Protection Agency.) NOTE: The MedPlus TotalAlert® Alarm Network is not intended for patient contact and ordinarily should not require disinfection. Page 6-28...
• Service the removed P.C. board at a static-free workstation that is properly grounded. • For shipping and storage, place the removed P.C. board in an antistatic pro- tective bag. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-29...
Joint Commission on Accreditation of Healthcare Organizations (JCAHO). PM and testing not only meet JCAHO requirements but will help ensure a long, operative life for the MedPlus TotalAlert® Alarm Network. PM will minimize downtime due to excessive wear.
General appearance Check cleanliness. Clean if necessary, see “Cleaning” on page 6-28. Contact BeaconMedæs Technical Support for information on having these tests performed by a BeaconMedæs Service Representative. MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728) Page 6-31...
Tool and Supply Requirements Chapter 6: General Procedures Tool and Supply Requirements To service the MedPlus TotalAlert® Alarm Network, the following tools and sup- plies are required: • 5/32" hex head wrench • Small slotted screwdriver • Phillips head screwdriver, various sizes •...
Page 365
Tool and Supply Requirements Chapter 6: General Procedures NOTES: Page 6-34 MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Need help?
Do you have a question about the MedPlus TotalAlert and is the answer not in the manual?
Questions and answers
I an looking for a circuit board for one of your products. The # on the circuit board is, HCRB-0000-0000/D205504 where can I get one?
I found a PC board in a manual. How do I get one.
Contact BeaconMedæs Technical Support for information on obtaining a PC board for the MedPlus TotalAlert system.
This answer is automatically generated
The PC board I **** looking for is Area Alarm Communications Board
The Area Alarm Network Communications Board for the BeaconMedaes TotalAlert provides the same functions as the Area Alarm Connector P.C. Board and also connects to the facility’s Ethernet. This connection allows optional communication with the Master Alarm, enabling it to monitor the Area Alarm.
This answer is automatically generated
Med plus total alert I **** getting a A 03 on Oxygen panel
An A03 error on the Oxygen panel of the BeaconMedæs MedPlus TotalAlert indicates a Transducer Communication Error. It suggests that the transducer may not be connected properly. The troubleshooting steps involve checking the connection, and if the issue persists, replacing the transducer.
This answer is automatically generated
Regarding My Medplus Total Alert area alarm I need to replace the transducer P6819 Additional info. from the transducer HRTM-RETR-NTRG/206261-N
@Ed Leininger Need to order the replacement transducer
To replace the transducer P6819 for the BeaconMedæs MedPlus TotalAlert area alarm, follow these steps:
1. Check if the transducer shows a slow steady flash on its heartbeat LED. If yes, replace the transducer.
2. Ensure the transducer is connected properly. If not, reconnect it properly.
3. Inspect the transducer wiring for pinching. If wiring is pinched, replace the transducer wiring.
4. If the issue persists after these steps, replace the transducer following procedure 4.23 (referenced on page 4-62 of the manual).
Always disconnect power before servicing and follow standard safety procedures.
This answer is automatically generated