8.7 Commissioning and Start-up behavior
Start-up on delivery
HB300 | CPU | 013-CCF0R00 | en | 16-40
[1] 1./last bus participant
[2] further participants
CAUTION!
The terminating resistor is only effective, if the connector is installed at a
bus participant and the bus participant is connected to a power supply.
The tightening torque of the screws to fix the connector to a device must
not exceed 0.02Nm!
A complete description of installation and deployment of the terminating
resistors is delivered with the connector.
1.
Loosen the screw.
2.
Lift contact-cover.
3.
Insert both wires into the ducts provided (watch for the correct line colour as below!)
4.
Please take care not to cause a short circuit between screen and data lines!
5.
Close the contact cover.
6.
Tighten screw (max. tightening torque 0.08Nm).
The green line must be connected to A, the red line to B!
In delivery the CPU is overall reset. The PROFIBUS part is deactivated and its LEDs are
off after Power ON.
Option: PROFIBUS communication
Commissioning and Start-up behavior