Communication
10.4 Communication via SINAMICS Link
10.4.5

Communication failure when booting or in cyclic operation

If at least one sender does not correctly boot after commissioning or fails in cyclic operation,
then alarm A50005 is output to the other nodes: "Sender was not found on the SINAMICS
Link."
The message contains the number of the faulted node. After you have resolved the fault at
the node involved and the system has identified the node, the system automatically
withdraws the alarm.
If several nodes are involved, the message occurs a multiple number of times consecutively
with different node numbers. After you have resolved all of the faults, the system
automatically withdraws the alarm.
When a node fails in cyclic operation, in addition to alarm A50005, fault F08501 is output:
"COMM BOARD: Monitoring time, process data expired"
Function diagrams (see SINAMICS S120/S150 List Manual)
● 2211 Data transfer
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● r2050[0...19] CO: IF1 PROFIdrive PZD receive word
● p2051[0...14] CI: IF1 PROFIdrive PZD send word
● r2060[0...18] CO: IF1 PROFIdrive PZD receive double word
● p2061[0...26] CI: IF1 PROFIdrive PZD send double word
● p8811 SINAMICS Link project selection
● p8812[0...1] SINAMICS Link settings
● p8835 CBE20 firmware selection
● p8836 SINAMICS Link address
● p8870 SINAMICS Link telegram word PZD receive
● p8871 SINAMICS Link telegram word PZD send
● p8872 SINAMICS Link address PZD receive
680
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2