Bypass With Synchronization With Overlap - Siemens Sinamics S120 Function Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

● When the drive is started up again after POWER ON, the status of the bypass contactors
● Changing the converter into "Ready to start and bypass" status after powering up, is of a
● Monitoring of the motor temperatures using temperature sensors is active while the
● The two motor contactors must be designed for switching under load.
Prerequisite
The bypass function is only possible for encoderless closed-loop speed control (p1300 = 20)
or V/f control (p1300 = 0...19) and when an induction motor is used.
Commissioning the bypass function
The bypass function is part of the function module "technology controller" that can be
activated when using the commissioning Wizard. Parameter r0108.16 indicates whether it
has been activated.
4.25.1

Bypass with synchronization with overlap

Description
When "bypass with synchronization with overlap (p1260 = 1)" is activated, then motor is
transferred, synchronized to the line supply and is also retrieved again. During the
changeover, the two contactors K1 and K2 are simultaneously closed for a time (phase lock
synchronization).
A reactor is used to de-couple the drive converter from the line supply - the uk value for the
reactor is 10% +/- 2%.
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
is evaluated. After powering up, the converter can thereby change straight into "Ready to
start and bypass" status. This is only possible if the bypass is activated via a control
signal, the control signal (p1266) is still present once the system has been ramped up,
and the automatic restart function (p1200 = 4) is active.
higher priority than switching back on automatically.
converter is in one of two statuses "Ready to start and bypass" or "Ready for operation
and bypass".
Note
The examples contained in the following descriptions are only basic circuits designed to
explain the basic function. The dimensions of specific circuit configurations (contactors,
protective equipment) must be calculated for specific systems.
Vector control
4.25 Bypass