Siemens Sinamics S120 Function Manual page 83

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

NOTICE
Negative values at r1534 or positive values at r1535 represent a minimum torque for the
other torque directions and can cause the drives to rotate if no counteractive load torque is
generated (see function diagram 5630 in the SINAMICS S120/S150 List Manual).
Example: Torque limits with or without offset
The signals selected via p1522 and p1523 include the torque limits parameterized via p1520
and p1521.
Figure 3-10
Activating the torque limits
1. Use parameters to select the torque limiting source.
2. Use a control word to specify the torque limiting mode.
3. The following can also be carried out if necessary:
Examples
● Travel to fixed stop
● Tension control for continuous goods conveyors and winders
Function diagrams (see SINAMICS S120/S150 List Manual)
● 5610 Torque limiting/reduction/interpolator
● 5620 Motor/generator torque limit
● 5630 Upper/lower torque limit
● 5640 Mode changeover, power/current limiting
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Example: Torque limits with or without offset
– Select and activate additional limitations.
– Set the torque offset.
Servo control
3.5 Torque setpoint limitation
81