6.4 Sinusoidal filter

Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p0105 Activate/deactivate drive object
● r0106 Drive object active/inactive
● p0125 Activate/deactivate power unit component
● r0126 Power unit component active/inactive
● p0145 Activate/deactivate encoder interface
● r0146 Encoder interface active/inactive
● p9495 BICO response to deactivated drive objects
● p9496 Re-establish BICO to the now activated drive objects
● r9498[0 ... 29] BICO BI/CI parameter to deactivated drive objects
● r9499[0 ... 29] BICO BO/CO parameter to deactivated drive objects
6.4
Sinusoidal filter
Description
The sine-wave filter limits the rate of rise of voltage and the capacitive charge/discharge
currents that usually occur with inverter operation. They also prevent additional noise caused
by the pulse frequency. The service life of the motor is the same as that with direct line
operation.
CAUTION
If a sine-wave filter is connected to the Power Module or Motor Module, the converter must
be activated during commissioning (p0230 = 3) to prevent the filter from being destroyed.
If a sine-wave filter is connected to the Power Module or Motor Module, the Power Module
or Motor Module must not be operated without a connected motor because otherwise the
filter can be destroyed.
238
CAUTION
If a drive in a Safety Integrated line-up is deactivated via p0105, r9774 is not read
correctly because the signals from the deactivated drive are no longer updated.
Remedy: Remove this drive from the group before you deactivate it. See also: /FH1/
SINAMICS S120 Function Manual, Chapter Safety Integrated Basic Functions.
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Drive functions