Siemens Sinamics S120 Function Manual page 587

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Field
Format
No. of values
Error values
Values
Error values in DPV1 parameter responses
Table 10- 53 Error values in DPV1 parameter responses
Error
value
0x00
Illegal parameter number
0x01
Parameter value cannot be changed
0x02
Lower or upper value limit exceeded
0x03
Invalid subindex
0x04
No array
0x05
Wrong data type
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Data type
Unsigned8
The format and number specify the adjoining space containing values in the telegram.
Data types in conformity with PROFIdrive Profile shall be preferred for write access. Bytes,
words and double words are also possible as a substitute.
Unsigned8
Specifies the number of subsequent values.
Unsigned16
The error values in the event of a negative response.
If the values make up an odd number of bytes, a zero byte is appended. This ensures the
integrity of the word structure of the telegram.
Unsigned16
The values of the parameter for read or write access.
If the values make up an odd number of bytes, a zero byte is appended. This ensures the
integrity of the word structure of the telegram.
Meaning
10.1 Communication according to PROFIdrive
Values
0x02
0x03
0x04
0x05
0x06
0x07
0x08
Other values
0x40
0x41
0x42
0x43
0x44
0x00 ... 0xEA
0x0000 ... 0x00FF
0x0000 ... 0x00FF
Access to a parameter which does not exist.
Modification access to a parameter value which cannot be
changed.
Modification access with value outside value limits.
Access to a subindex which does not exist.
Access with subindex to an unindexed parameter.
Modification access with a value which does not match the
data type of the parameter.
Data type integer8
Data type integer16
Data type integer32
Data type unsigned8
Data type unsigned16
Data type unsigned32
Data type floating point
See PROFIdrive profile V3.1
Zero (without values as a positive
subresponse to a write request)
Byte
Word
Double word
Error
No. 0 ... 234
Limited by DPV1 telegram length
Significance of the error values
→ refer to the following table "Error
values in the DPV1 parameter
responses"
Remark
Communication
Remark
Additional
info
Subindex
Subindex
Subindex
585

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents