4.25 Bypass
● Pulses are enabled. Since "Synchronize" is set before "Pulse enable", the converter
● After the motor has been synchronized to the line frequency, line voltage and line phase,
● The bypass mechanism evaluates this signal and closes contactor K1. The signal is
● Once contactor K1 has reported "closed" status, contactor K2 is opened and the motor is
4.25.2

Bypass with synchronization without overlap

Description
When "bypass with synchronization without overlap (p1260 = 2)" is activated, contactor K2 to
be closed is only closed when contactor K1 has opened (anticipatory type synchronization).
During this time, the motor is not connected to the line supply so that its speed is determined
by the load and the friction. Phasing of the motor voltage before synchronization must be set
such that there is an "initial jump" upstream of the supply to which synchronization should be
carried out. This is done by setting the synchronization setpoint (p3809). As a result of the
motor braking in the short time during which, both contactors are open, when closing
contactor K2, a phase and frequency difference of approximately zero is obtained.
For the function to run correctly, the moment of inertia of the drive and the load must be
sufficient.
Note
A sufficiently high moment of inertia
is characterized by a change in the motor speed when opening contactors K1 and K2 that is
approximately equal to the rated slip and no more. The electrical angle difference of the
motor relative to the phase difference of the line supply may only change to the extent that it
can be compensated using p3809.
It is no longer necessary to use the de-coupling reactor after having determined the
synchronizing setpoint (p3809).
208
interprets this as a command to retrieve a motor from the supply and to take it over.
the synchronizing algorithm reports this status.
internally evaluated - BICO wiring is not required.
operated again on the converter.
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2