Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p8835 CBE20 firmware selection
● r8858[0...39] COMM BOARD read diagnostics channel
10.3.6.1

EtherNet/IP

SINAMICS S120 supports the communication with the fieldbus EtherNet Industrial Protocol
(EtherNet/IP or also EIP). EtherNet/IP is an open standard based on Ethernet, which is
predominantly used in the automation industry. EtherNet/IP is supported by the Open
DeviceNet Vendor Association (ODVA).
For communication with EtherNet/IP, an Ethernet CBE20 option board is required. By setting
p8835 = 4, you can choose the communication profile EtherNet/IP. After POWER ON, the
profile becomes active.
10.3.7
PN gate
The SINAMICS PN Gate is a PROFINET solution for control manufacturers and machine
builders to simply integrate an interface into customers own PROFINET networks. The
CBE20 option board is the interface between PROFINET and the customer's control
network. The Control Unit CU320-2PN communicates via the CBE20 with the network of the
customer.
Figure 10-45 Schematic diagram of SINAMICS PN Gate
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
10.3 Communication via PROFINET IO
Communication