Siemens Sinamics S120 Function Manual page 213

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Example
After activating the bypass function without synchronization (p1260 = 3) the following
parameters still have to be set:
Table 4- 11
p1262 =
p1263 =
p1264 =
p1265 =
p1266 =
p1267.0 =
p1267.1 =
p1268
P1269[0] =
P1269[1] =
p3800 = 1
p3802 = r1261.2
Function diagrams (see SINAMICS S120/S150 List Manual)
● 7020 Synchronization
Overview of important parameters (see SINAMICS S120/S150 List Manual)
Bypass function
● p1260 Bypass configuration
● r1261.0...9 CO/BO: Bypass control/status word
● p1262[0...n] bypass deadtime
● p1263 Debypass delay time
● p1264 Bypass delay time
● p1265 Bypass speed threshold
● p1266 BI: Bypass control command
● p1267 bypass changeover source configuration
● p1268 BI: Bypass feedback signal synchronization completed
● p1269[0...1] BI: Bypass switch feedback signal
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Parameter settings for non-synchronized bypass function with overlap
Parameter
Setting of the deadtime for non-synchronized bypass
Setting of the delay time to switch back to converter operation for non-
synchronized bypass
Setting of the delay time to switch to line operation for non-synchronized
bypass
Setting of the speed threshold for activating the bypass (for p1267.1 = 1)
Setting of the signal source for the control command to the bypass (for
p1267.0 = 1)
Trigger signal setting for bypass function
Setting of the signal source for the feedback signal
"synchronization completed"
Setting of the signal source for the feedback signal of contactor K1
Setting of the signal source for the feedback signal of contactor K2
The internal voltages are used for synchronization.
Synchronizer activation is triggered by the bypass function.
Description
Vector control
4.25 Bypass
211