Fast DC link discharge (booksize)
It is only possible to quickly discharge the DC link via the Braking Module for the booksize
format. It is activated via binector input p3863 and started after the line contactor opens and
the adjustable delay time (p3862) has expired. The fast discharge is completed when the line
contactor contact closes.
NOTICE
A fast DC link discharge requires the use of a line contactor with feedback signal (p0860)
that is controlled via r0863.1.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● r0108.26 Drive object function module - Braking Module external
● p3860 Braking Module number of modules connected in parallel
● r3861.0...7 BO: Braking Module inhibit/acknowledgement
● p3862 Braking Module DC link fast discharge delay time
● p3863 BI: Braking Module activate DC link fast discharge
● p3864.0...7 BO: Braking Module DC link fast discharge
● p3865[0...7] BI: Braking Module pre-alarm I*t shutdown
● p3866[0...7] BI: Braking Module fault
7.5

Cooling unit

Features
● Automatically activated when using liquid-cooled power units
● Evaluation of an external sensor for leakage water
● Evaluation of an external sensor for liquid flow
● Evaluation of an external sensor for conductivity
● Monitoring the liquid intake temperature using external temperature sensors
● Monitoring the flow rating using internal temperature sensors
● Evaluation of signals transmitted from the PLC of the cooling unit
● Acknowledging cooling unit faults
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Function modules
7.5 Cooling unit
329