Cont rol of the safety functions

5.5 Response for a communication failure via PROFIsafe or to the TM54F

5.5
Response for a communication failure via PROFIsafe or to the
TM54F
Factory setting for the response to communication failure
In the following cases, the drive responds with a STOP A.
● PROFIsafe communication to the higher-level control has failed.
● DRIVE-CLiQ communication to the TM54F has failed.
5.5.1

STOP B as response to communication failure with PROFIsafe control

If, for a communication failure, the axis coasting down can result in subsequent damage, as
response to the communication failure, instead of a STOP A, you can select that the axis is
stopped along a ramp.
Precondition
You have enabled Safety Integrated Extended Functions or Basic Functions.
Communication failure
In this context, communication failure can mean the following:
● Interruption or disturbance in PROFIsafe communication
● The higher-level controller (F-CPU) is in the STOP state
Drive response
Parameter p9612 defines the drive stop response when PROFIsafe communication fails:
● p9612 = 0: STOP A
● p9612 = 1: STOP B
Not e
For the selected STOP B stop response, in order to ensure that the OFF3 ramp is actually
maintained, when just using the Safety Basic Functions, the following must be carefully
observed:
• The STOP F to STOP A (p9658, p9858) transition time must be set to greater than or
equal to the SS1 delay time (p9652, p9852).
• If a higher-level control system responds to the drive fault by withdrawing the controller
enable signals, for faults F01611 and F30611, the message type must be changed to
alarm (p2118, p2119).
196
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Safety Integrated