● 4 motor contactors with positively-driven auxiliary contacts (3 NC contacts, 1 NO contact)
● 4 motors, 1 Control Unit, 1 infeed, and 1 Motor Module
Table 11- 1
p0130
p0180
p0186[0...3]
p0820, p0821
p0822 to p0824
p0826[0...3]
p0827[0...3]
r0830.0 to r0830.3
p0831[0...3]
p0833.0..2
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Figure 11-2
Example of motor changeover
Settings for the example
Parameter
4
4
0, 1, 2, 3
Digital inputs DDS
selection
0
0, 1, 2, 3
0, 1, 2, 3
Digital outputs,
contactors
Digital inputs, auxiliary
contacts
0, 0, 0
Settings
Configure 4 MDS.
Configure 4 DDS.
The MDS are assigned to the DDS.
The digital inputs for motor changeover via DDS
selection are selected. Binary coding is used (p0820 =
bit 0 etc.).
Different numbers indicate a different thermal model
Assigning the bit from r0830 to the MDS. If p0827[0] =
1, for example, bit p0830.1 is set when MDS0 is
selected via DDS0.
The digital outputs for the contactors are assigned to
the bits.
The digital inputs for the feedback signal of the motor
contactors are assigned.
The drive controls the contactor circuit and pulse
inhibition. Parking bit (Gn_ZSW14) is set.
Applications
11.2 Description
Remark
685