Siemens Sinamics S120 Function Manual page 241

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Usage restrictions for sine-wave filters
The following restrictions must be taken into account when a sine-wave filter is used:
● The output frequency is limited to a maximum of 150 Hz.
● The modulation type is permanently set to space vector modulation without
● Maximum permissible motor cable lengths:
● Other restrictions: Refer to the manuals
Note
If a filter cannot be parameterized (p0230 < 3), this means that a filter has not been provided
for the component. In this case, the drive converter must not be operated with a sine-wave
filter.
Table 6- 6
Parameter number
p0233
p0234
p0290
p1082
p1800
p1802
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
overmodulation. This reduces the maximum output voltage to approx. 85 % of the rated
output voltage.
– Unshielded cables: max. 450 m
– Shielded cables: max. 300 m
– SINAMICS S120 AC Drive
– SINAMICS S120 Chassis power units
– SINAMICS S120 Liquid Cooled Chassis power units
Parameter settings for sine-wave filters
Power unit motor reactor
Power unit sine-wave filter
capacitance
Power unit overload response
Maximum rotational speed
Pulse frequency
Modulator modes
Name
Filter inductance
Filter capacitance
Disable pulse frequency reduction
Fmax filter/pole pair number
Nominal pulse frequency of the filter
Space vector modulation without
overmodulation
Basic functions
6.4 Sinusoidal filter
Setting
239