Direction Of Rotation Limiting And Direction Of Rotation Changeover - Siemens Sinamics S120 Function Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

● r1073[C] CO: Main setpoint effective
● p1075[C] CI: Supplementary setpoint
● p1076[C] CI: Supplementary setpoint scaling
● r1077[C] CO: Supplementary setpoint effective
● r1078[C] CO: Total setpoint effective
Parameterization with STARTER
The "speed setpoint" parameter screen is selected via the following symbol in the toolbar of
the STARTER commissioning tool:
Figure 2-7
2.7

Direction of rotation limiting and direction of rotation changeover

Description
A reversing operation involves a direction of rotation reversal. Selecting setpoint inversion
p1113[C] can reverse the direction of rotation in the setpoint channel.
Parameter p1110[C] or p1111[C] can be set respectively to prevent input of a negative or
positive setpoint via the setpoint channel. However, the following settings for minimum speed
(p1080) in the setpoint channel are still operative. With the minimum speed, the motor can
turn in a negative direction, although p1110 = 1 is set.
Figure 2-8
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
2.7 Direction of rotation limiting and direction of rotation changeover
STARTER symbol for "speed setpoint"
Direction of rotation limiting and direction of rotation reversal
Extended setpoint channel
59