Features
● Field weakening up to approx. 1.2 * rated speed (this depends on the drive converter
● Flying restart
● Vector closed-loop speed and torque control
● Vector V/f control
● Motor identification
● Speed controller optimization (rotating measurement)
● Thermal protection via temperature sensor (PTC/KTY)
● All encoders that can be connected to an SMC10, SMC20 or SMC30 are supported.
● Operation with or without encoder is possible.
Supplementary conditions
Depending on the terminal voltage and load cycle, the maximum torque can be taken from
the motor data sheets / project design instructions.
Commissioning
We recommend the following points when commissioning:
● Commissioning wizard in STARTER
● Motor identification (standstill (static) measurement (p1910)
● Rotating measurement (p1960)
The optional motor data can be entered if it is known. Otherwise, they are estimated using
the rating plate data or are determined using a motor identification routine or speed controller
optimization.
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
supply voltage and the motor data, also refer to supplementary conditions).
The motor identification routine and the "rotating measurement" (p1900) can be activated
from the commissioning wizard in STARTER.
4.17 Instructions for commissioning induction motors (ASM)
Vector control
187