Reactive Current Control - Siemens Sinamics S120 Function Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Infeed
1.1 Active Infeed
1.1.6

Reactive current control

A reactive current setpoint can be set to compensate the reactive current or to stabilize the
line voltage in infeed mode. The total setpoint is the sum of the fixed setpoint p3610 and the
dynamic setpoint via the connector input p3611.
● The direction of rotation of the line supply is compensated automatically with reactive
● The closed-loop control limits the reactive current setpoint dynamically in such a way that
● The reactive current demand of a line filter selected in the configuration wizard is
● The reactive power setpoint of the Active Infeed Module with respect to the line supply
Function diagrams (see SINAMICS S120/S150 List Manual)
● 1774 Overviews - Active Infeed
● 8946 Current pre-control / current controller / gating unit (p3400.0 = 0)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p3610 Infeed reactive current fixed setpoint
● p3611 CI: Infeed reactive current supplementary setpoint
30
current control.
– A negative reactive current setpoint causes an inductive reactive current
– A positive reactive current setpoint generates a capacitive reactive current
the sum of the active current setpoint and the reactive current setpoint does not exceed
the maximum device current.
automatically supplied by the Active Infeed Module. This means that the display value of
the actual reactive current setpoint in r0075 no longer corresponds with the
parameterized total reactive current setpoint.
can be obtained by multiplying the parameterized total reactive current setpoint by 1.73 *
rated line voltage.
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Drive functions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents