p3410 is automatically set to 0 when one of the two identification routines (p3410 = 4 or
p3410 = 5) completes successfully.
Note
Identification using p3410 = 5 should preferably be used.
It may be necessary to reset the closed-loop controller to the factory settings if an
identification run was unsuccessful, for example.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p3410 Infeed identification method
● r3411 Infeed inductance identified
● r3412 Infeed DC-link capacitance identified
● p3560 Infeed Vdc controller proportional gain
1.1.5

Active Infeed open-loop control

Description
The Active Line Module can be controlled via the BICO interconnection using terminals or
the fieldbus. The operating status is indicated on the operating display r0002. The missing
enable signals for operation (r0002 = 00) are mapped in parameter r0046. The EP terminals
(enable pulses) must be connected in accordance with the Manual of the corresponding
power units. The drive unit must have been commissioned for the first time.
Acknowledging faults
Faults that are still present but the causes of which have been rectified can be
acknowledged using a 0/1 edge at the "1. Acknowledge faults" signal (p2103).
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Infeed
1.1 Active Infeed
27