Siemens Sinamics S120 Function Manual page 523

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Bit
Meaning
Note:
The ramp-function generator cannot be frozen via p1141 in jog mode (r0046.31 = 1).
6
Enable speed setpoint
7
Acknowledge fault
Note:
Faults are acknowledged at a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.
8
Reserved
9
Reserved
10
Master control by PLC
Note:
This bit should not be set "1" until PROFIdrive has returned an appropriate status via ZSW1_BM.9 = "1".
11
Reserved
...
15
STW2_BM (control word 2, metal industry)
See function diagram [2426].
Table 10- 11 Description of STW2_BM (control word 2, metal industry)
Bit
Meaning
0
Command data set selection CDS bit 0
1
Command data set selection CDS bit 1
2
Drive data set selection DDS, bit 0
3
Drive data set selection DDS, bit 1
4
Drive data set selection DDS, bit 2
5
Bypass ramp-function generator
6
Reserved
7
Enable load compensation
8
Enable droop
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
10.1 Communication according to PROFIdrive
Remarks
0
Freeze ramp-function generator
1
Enable setpoint
0
Inhibit setpoint
Set ramp-function generator input to zero
0/1
Acknowledge fault
0
No effect
-
-
-
-
1
Master control by PLC
This signal must be set so that the process data
transferred via PROFIdrive are accepted and
become effective.
0
PLC has no master control
Process data transferred via PROFIdrive are
rejected - i.e. assumed to be zero.
-
-
Remarks
-
-
-
-
-
-
-
-
-
-
1
Function module "Extended setpoint generator"
must be selected
-
-
1
Set speed controller I component
1
Set scaling for droop feedback (not applicable
to servo)
Communication
Parameter
BI: p1142
BI: p2103
-
-
BI: p0854
-
Parameter
p0810
p0811
p0820
p0821
p0822
p1122
-
p1477
p1492
521