Communication
10.1 Communication according to PROFIdrive
Bit
Meaning
1
Torque utilization < p2194
Application:
This message indicates that the motor is overloaded and appropriate measures need to be taken to rectify the
situation (e.g. stop the motor or reduce the load).
2
|n_act| < p2161
Note:
The message is parameterized as follows:
p2161 Threshold value
p2150 Hysteresis
Application:
To protect the mechanics, the gear stages are not switched mechanically until the speed is less than the set
threshold value.
3
|n_act| ≤ p2155
544
Remarks
0
Ramp-function generator active
The ramp-up procedure is still active once the
speed setpoint has been changed.
0/1
Ramp-up ends.
The end of the ramp-up procedure is detected as
follows:
The speed setpoint is constant,
and
The actual speed value is within the tolerance
bandwidth and has reached the speed setpoint,
and
The delay time (p2166) has elapsed.
1
Torque utilization < p2194
The current torque utilization is less than the set
torque utilization threshold (p2194),
or
Ramp-up is not yet complete.
0
Torque utilization > p2194
The current torque utilization is greater than the
set torque utilization threshold (p2194).
1
|n_act| < p2161
The absolute actual speed value is less than the set
threshold value (p2161).
0
|n_act| ≥ p2161
The absolute actual speed value is greater than or
the same as the set threshold value (p2161).
1
|n_act| ≤ p2155
The absolute actual speed value is less than or the
same as the set threshold value (p2155).
0
|n_act| > p2155
The absolute actual speed value is greater than the
set threshold value (p2155).
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Parameter
BO: r2199.11
BO: r2199.0
BO: r2197.1
Drive functions