Siemens Sinamics S120 Function Manual page 649

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Name
T_IO_Output_valid
Dx
R or Rx
Setting criteria for times
● Cycle (T
● T
● Settings and optimization can be done via a tool (e.g. HWConfig in SIMATIC S7).
User data integrity
User data integrity is verified in both transfer directions (IO controller <––> IO device) by a
sign of life (4-bit counter).
The sign-of-life counters are incremented from 1 to 15 and then start again at 1.
● IO controller sign of life
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Limit value
The time after which the new control output data (setpoints) are available
for the drive object.
Data_Exchange
This service is used to implement user data exchange between the IO
controller and IO device 1 - n.
Computation time, current or position controller
)
DC
– T
must be set to the same value for all bus nodes. T
DC
– T
> T
and T
DC
CA_Valid
T
is thus large enough to enable communication with all bus nodes.
DC
and T
IO_Input
IO_Output
– Setting the times in T
time in the position control loop.
– T
> T
+ T
IO_Output
CA_Valid
– STW2.12 ... STW2.15 are used as the IO controller sign of life.
– The IO controller sign-of-life counter is incremented in each IO controller application
cycle (T
).
CACF
– The number of sign-of-life errors tolerated can be set via p0925.
– p0925 = 65535 deactivates sign-of-life monitoring on the IO device.
≧ T
DC
IO_Output
and T
to be as short as possible reduces the dead
IO_Input
IO_Output
IO_Output_MIN
10.3 Communication via PROFINET IO
Description
is a multiple of SendClock.
DC
Communication
647