Basic functions
6.6 dv/dt filter compact plus Voltage Peak Limiter
Restrictions
The following additional restrictions must be taken into account when a dv/dt filter is used:
● The output frequency is limited to a maximum of 150 Hz.
● Maximum permissible motor cable lengths:
● Other restrictions: Refer to the manuals
Commissioning
During commissioning, you must activate the dv/dt filter with p0230 = 2.
242
– Shielded cables: Max. 100 m
– Unshielded cables: Max. 150 m
– SINAMICS S120 AC Drive
– SINAMICS S120 Chassis power units
– SINAMICS S120 Liquid Cooled Chassis power units
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Drive functions