Applications

11.1
Switching on a drive object X_INF using a VECTOR drive object
Description
Figure 11-1
Using this BICO interconnection, a drive object (DO) X_INF
VECTOR drive object. This switch on version is mainly used for drive units in the chassis
format if a single Infeed Module and one Motor Module can be used. If an application
requires an automatic restart function (AR), you can proceed as follows:
● The automatic restart function is activated on the VECTOR drive object (p1210).
● In addition to the automatic restart function, the following conditions must be fulfilled:
Individual steps when restarting:
● After the line supply returns and the electronics has booted, the faults that have occurred
● The faults of the X_INF drive object are acknowledged via the BICO connection from
● The ON command (p0840) for the Infeed Module is generated via the binector output
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
BICO interconnection
– The flying restart function (p1200) must be activated on the VECTOR drive object so
that a flying restart can be made.
– The supply voltage must be reliably available at the Infeed Module (before the switch-
on command, an existing line contactor or motor relay must have closed).
at the VECTOR drive object as a result of its automatic restart are acknowledged
depending on the settings in p1210.
r1214.3 to p2105.
"control line contactor" of the VECTOR drive object (p0863.1).
11
can be switched-in using a
1)
683