Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p3410 Infeed identification method
● p3421 Infeed inductance
● p3422 Infeed DC link capacitance
1.2.2

Smart Infeed open-loop control

The Smart Line Module can be controlled via the BICO interconnection, e.g. using terminals
or the fieldbus. The operating status is indicated on the operating display r0002. The missing
enable signals for operation (r0002 = 00) are mapped in parameter r0046. The EP terminals
(enable pulses) must be connected in accordance with the Manual of the corresponding
power units. The drive unit must have been commissioned for the first time.
Acknowledging faults
Faults that are still present but the causes of which have been rectified can be
acknowledged using a 0/1 edge at the "1. Acknowledge faults" signal (p2103).
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Infeed
1.2 Smart Infeed