Safety Integrated basic functions
9.8 Control via terminals on the Control Unit and Motor/Power Module
Example: Terminal groups
It must be possible to select/deselect "Safe Torque Off" separately for group 1 (drives 1 and
2) and group 2 (drives 3 and 4).
For this purpose, the same grouping for "Safe Torque Off" must be realized both for the
Control Unit and the Motor Modules.
Figure 9-3
Example: Grouping terminals with Motor Modules Booksize and CU320-2
Information on the parallel connection of chassis type Motor Modules
When chassis type Motor Modules are connected in parallel, a safe AND element is created
on the parallel drive object. The number of indexes in p9620 corresponds to the number of
parallel chassis components in p0120.
9.8.1
Simultaneity and tolerance time of the two monitoring channels
The "Safe Torque Off" function must be selected/deselected simultaneously in both
monitoring channels using the input terminals and is only effective for the associated drive.
1 signal: Deselecting the function
0 signal: Selecting the function
476
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Drive functions