Simultaneity And Tolerance Time Of The Two Monitoring Channels - Siemens Sinamics S120 Function Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

5.2.1

Simultaneity and tolerance time of the two monitoring channels

The monitoring functions must be selected/deselected simultaneously in both monitoring
channels via the input terminals and only have an effect on the associated drive.
● 1 signal: Deselecting the function
● 0 signal: Selecting the function
The time delay that is unavoidable due to mechanical switching processes, for example, can
be adapted via parameters. The tolerance time, within which selection/deselection of the two
monitoring channels must occur if they are to be considered "simultaneous," is set in the
following parameters:
● p9650 (Basic Functions)
● p10002 (Extended Functions)
Not e
P arameterization of the tolerance time
In order to avoid that faults are incorrectly initiated, at these inputs the tolerance time must
always be set shorter than the shortest time between two switching events (ON/OFF,
OFF/ON).
● If the monitoring functions are not selected/deselected within the tolerance time, this is
detected by the cross-check, and the following fault (STOP F) is output.
– F01611 (Basic Functions)
– C01770 (Extended Functions)
For STO: In this case, the pulses have already been canceled as a result of the selection
of "Safe Torque Off" on one channel.
Not e
Timing between t he switching operations in t he Basic Functions
Message F01611 with fault value 1000 is output if switching operations occur too
frequently. The cause depends on the type of control:
• The signals are continually changing at the F-DI.
• STO is being permanently initiated via PROFIsafe (also as subsequent response).
Within the time 5 × p9650, there must be at least two switching operations at the
terminals or via PROFIsafe with a minimum time between them of p9650.
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
5.2 Control signals by way of terminals on the Control Unit and Motor / Power Module
Control of the safety functions
171

Hide quick links: