If motor temperature is not monitored by a motor temperature sensor, motor overload
monitoring is to be activated. Among other things nominal current
constant
4.11.5.2 Speed variable l
The preset standard solution referring to the constant maximum continuous current
throughout the total speed range is inadequate to many applications with synchronous
and asynchronous machines. Therefore, in the following implementation solutions are in-
troduced considering the speed-dependence of the maximum continuous current of the
2
l
t motor model.
Speed variable I2t overload monitoring of synchronous machines
I2t actual value
(
I
6.30
Motor I2t time constant (107.28) = 600 s
0
Function example of the motor l
Z107.28–
of the motor have to be specified correctly.
2
t overload monitoring