4.6
Set Value Generators

4.6.1.4 Description of the Parameters

110.1
Status
Status of the ramp function generator
31 ... 22
Comments:
m Bit 13:
408
Parameter manual b maXX BM3000
Document no.: 5.12001.07
of 820
Bit
Meaning
0
1: Ramp generator is switched on
3 ... 1
Reserved
4
1: FG output is set internally to 0 (FG INHIBIT)
5
1: FG has been halted on the ramp (FG STOP)
6
1: FG input is set internally to set value 0 (FG ZERO)
7
1: Quick Stop ramp is active (FG QSTOP)
8
1: Ramp-up is active
9
1: Ramp-down is active
10
1: Braking ramp ended
11
Reserved
12
1: FG output = FG input (set value reached)
13
Status input set value
0: Input set value is constant
1: Input set value is interpolated
14
1: Controlled stop is active
15
1: SS1 stop is active
16
1: Set Value inhibit has blocked negative set value (see 110.2 Mode Bit 0)
17
1: Set Value inhibit has blocked positive set value (see 110.2 Mode Bit 1)
18
1: Run in negative direction with hardware limit switch prevented
19
1: Run in positive direction with hardware limit switch prevented
20
Absolute value limitation of the input set value to an allowed minimum
Z110.16–
value
21
Absolute value limitation of the input set value to an allowed maximum
Z110.15–
value
Reserved
This bit is changed, if the interpolator set value cycle ramp function generator cycle
is active. The bit is deleted at constant input set value or set value failure. The ramp
function generator input set value is interpolated from the set value cycle to the ramp
function generator cycle (1 ms).