Description Of The Parameters - Baumuller b maXX BM3000 Operating Manual

Parameter
Hide thumbs Also See for b maXX BM3000:
Table of Contents

Advertisement

Description of the Software Modules and Parameters

4.4.11.3 Description of the Parameters

117.1
Status digital outputs
Status of the digital outputs. Bits 1 ... 0 display the hardware status, i.e., whether the par-
ticular output has been set active.
117.2
Mode digital output 1
Operating mode of digital output 1. Bits 3 ... 0 are used for setting the comparison oper-
ator to the bit pattern which was set as a parameter.
117.4
Source number digital output 1
Number of the parameter to be compared which is to activate Digital Output 1.
Bit no.
0
Status of Output 1
1
Status of Output 2
31 ... 4
Reserved
Bit
3 ... 0
0000: Channel is deactivated
0001: ([Data] AND [Bit selection]) is equal to the [Bit pattern]
0010: ([Data] AND [Bit selection]) is not equal to the [Bit pattern]
0011: ([Data] AND [Bit selection]) is equal to ONE, i.e., [Data] has
at least one bit of the [Bit selection] set
0100: ([Data] AND [Bit selection]) is equal to ZERO, i.e., [Data] has
no bits of the [Bit selection] set
0101: ([Data] AND [Bit selection]) is greater than the [Bit pattern]
0110: ([Data] AND [Bit selection]) is less than the [Bit pattern]
0111 ... 1111 reserved
7 ... 4
0: No special function
1: Triggering of the motor holding brake
15 ... 8
Reserved
Meaning
0 = inactive
1 = active
0 = inactive
1 = active
Meaning
Parameter manual b maXX BM3000
Document no.: 5.12001.07
4
223
of 820

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B maxx bm2500

Table of Contents