Description of the Software Modules and Parameters
2 If the value of the Usd voltage
3 If the d-,q-currents were adjusted the breakdown torque factor at the SM can be grad-
Breakdown torque controller
At the controlled processing the maximum torque current is limited by a PI controller and
provides the maximum possible torque current to the available voltage. Because the max-
imum torque current is adjusted this process is independent to the set motor parameters.
The breakdown torque controller is activated at bit 4 of parameter
same time deactivates the breakdown torque parameters. The input values are the same
as at the field weakening controller except that there is an own factor (Z142.21–) for the
breakdown torque control there is an own factor. As soon as the required voltage increas-
es the set voltage the torque current is limited by the PI controller and the controller is
immediately initialized to the present torque current. It is recommended to parameterize
this factor higher than the field weakening limit factor (Z142.15–), so that the field weak-
ening controller always starts at first. The higher the present field current the lower the
present Uq voltage and due to this a higher torque can is available and a higher torque
can be reached.

4.7.4.2 Parameter overview

Functional block:
Number
Name
142.1
Field weakening mode
142.2
Field weakening faktor
142.3
P-Gain field weakening con-
troller
142.4
Field weakening controller
integral action time
142.5
Minimum field weak factor
142.6
Maximum output voltage
RMS
rent specification value can be set at half the motor-nominal current (if higher values
are required contact the motor manufacturer). 
mended to activate the breakdown torque limit
setting of the breakdown torque factor Z138.17–. If the Usd voltage is not limited to the
assumed values U
d,Max
torque limit
(Z138.1–
bit 5 to 1). If the Usd voltage is limited and the issue with the con-
trolled current remains then the field weakening should be controlled as described in
point 1 otherwise carry on with point 3. 
ually increased to receive more torque current. However, this leads to a higher field
current amplitude (lower power factor). Thereby, should be checked if the field weak-
ening controller is operating sufficiently and if the field current amplitude is adequate
(refer to point 1).
FbFieldweak [142]
Type
Min
UINT
0
FLOAT
0
FLOAT
0
FLOAT
0
FLOAT
0
FLOAT
0
Z47.21–
is above the (1/2)-fold U
(Z138.1–
it is recommended to activate the adaption for the breakdown
Max
Default Value Unit
0xFFFF
0
1
1
1000
0.002
10000
3000
1
0
1000
0
Parameter manual b maXX BM3000
Document no.: 5.12001.07
it is recom-
ph,Max
bit 2 to 1) by the standardized
Z138.1–
and at the
Factor
1:1
X
1:1
X
1/V
1:1
X
ms
1:1
X
1:1
X
V
1:1
X
4
501
of 820