4.7
Controllers

4.7.5.8 Description of the Two-level Controller Parameter with absolute Thresholds

151.1
Mode
Configuration of the absolute two-level controller
15 ... 6
151.2
Status
State of the absolute two-level controller
15 ... 1
151.3
Input
Parameter number of the input of the two-level controller. With value 0 no comparison to
absolute thresholds operates.
512
Parameter manual b maXX BM3000
Document no.: 5.12001.07
of 820
Bit
Meaning
0
0: Inactive
1: Active
1
Reserved
2
0: No absolute-value generation at actual value (comparison signed)
1: Absolute-value generation at actual value (symmetrical monitoring)
4 ... 3
Performance two-level-controller output
00: Standard performance (switch on accordant hysteresis)
01: Set output only once
10: Reset output only once
11: Reserved
5
0: No automatic reset by status word bit 15
1: Automatic reset by status word bit 15
Reserved
Bit
Meaning
0
0: Inactive
1: Active
Reserved
Baumüller Nürnberg GmbH