4.6 Output Status Setting for the Case of a CPU Stop Error

This function sets whether to stop or continue I/O data exchange with DP-Slaves when a
CPU stop error occurs on a QCPU or remote I/O station where the QJ71PB92V is
mounted.
(1) Output status setting for the case of a CPU stop error
4
- 23
4.6 Output Status Setting for the Case of a CPU Stop Error
POINT
(1) When the QJ71PB92V is installed in a redundant system, the setting
described in this section is not required.
The QJ71PB92V continues I/O data exchange with DP-Slaves until systems
A and B go down, regardless of the setting shown in this section.
(2) When the QJ71PB92D-compatible function is enabled, the setting described
in this section is invalid.
When the QJ71PB92D-compatible function is used, set the output status
setting for the case of a CPU stop error by the intelligent function module
switch setting. (
On GX Works2, set the output status for the case where a CPU stop error occurs.
Set desired output status in the intelligent function module detailed settings after
setting the I/O assignments of the QJ71PB92V.
Section 6.7)