3.4

Output Mode at Operating Status Change (STOP to RUN)

When the operating status is switched from RUN to STOP, the CPU module internally stores the outputs (Y) in the
RUN status and turns off all the outputs (Y). The status of the outputs (Y) when the CPU module is changed from
STOP to RUN can be selected from the following two options in the parameter setting.
• Output the output (Y) status prior to STOP. ("Previous state")
• Clear the output (Y) status. ("Recalculate (output is 1 scan later)")
(1) Application
This function is used to determine the status of outputs (whether to resume the outputs from the previous status
or not) when the operating status is changed from STOP to RUN in the holding circuit.
• When outputting the output (Y) status prior to STOP
X20
X21
Y0
• When clearing the output (Y) status
X20
X21
Y0
Start
Stop
button
button
RUN
ON
OFF
OFF
ON
OFF
RUN
ON
OFF
OFF
ON
OFF
STOP
STOP
RUN
STOP
STOP
RUN
CHAPTER 3 FUNCTIONS
125
3