D7024 | Operation and Installation Guide | 7.0 Control Panel Programming
7.6.5

Communication Tries

Shortcut:
0-PROG > 6-PROG ACC'NTS > 5-COMM. TRIES
The system always makes ten attempts to communicate
an event. The parameter determines after which attempt
the system indicates a failure condition. Do not select 1
because a failure is indicated whenever a report is sent.
The following window appears:
COMM ATTMPTS(_ _)
(01-10):_ _
Enter the information and press [#] to access the
preceding window.
7.6.6

Machine Bypass

Shortcut:
0-PROG > 6-PROG ACC'NTS > 6-MACH BYPASS
The downloading computer can dial back to connect
downloading if an answering machine answered the
telephone before the control panel. When this option is
selected and if the control panel detects the telephone
line ringing within 1 min of the last ringing cycle, it
answers on the first ring and seizes the telephone line.
The following window appears:
MACHINE BYPASS
_ _ _ _:YES(1)NO(0)
Enter the information and press [#] to access the
preceding window.
7.7

PROG Formats

PROG FORMATS
1- 4/2 ZONE REPT
2- 4/2 RPT CODS
3- BFSK RPT CDS
4- SIA SIL RPT
This feature uses hexadecimal digits 0 through F.
Because keys A through F are not available on the
keypad, the following keys substituted:
[A] = History
[B] = Test
[C] = Disable
52
[D] = Drill
[E] = Silence
[F] = Reset
7.7. 1

4/2 Zone Report

Shortcut:
0-PROG > 7-PROG FORMATS > 1-4/2 POINT
REPORTS
4/2 Reports have an event type (first digit) and a point
number (second digit). These reports apply to points,
and only when the 3/1 or 4/2 format is selected.
The following window appears:
4/2 ZONE RPT
0- FIRE ALRM D1
1- FIRE RSTR D1
2- WATERFLOW D1
3- SUPERVISE D1
4- TROUBLE D1
5- TRBL RSTR D1
6- DISABLE D1
7- DSBL RSTR D1
8- MONITOR
9- MORE
1.
Press the number key corresponding to your event
type selection (D1 = Digit#1).
2. Press [9] to access the second digit options, point
numbers, and access:
4/2 ZONE RPT
1- POINT 1 D2
2- POINT 2 D2
3- POINT 3 D2
4- POINT 4 D2
5- POINT 5 D2
6- POINT 6 D2
7- POINT 7 D2
8- POINT 8 D2
9- MORE
3. Press [9] to access the second digit options, point
numbers and access:
4/2 ZONE RPT
1- POINT 9 D2
2- POINT 10 D2
3- RETURN TO D1