On-Board Points; Point Sensor Loops; Single Eol (And No Eol) Resistor Circuit Style - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

72
en | On-board points
12

On-board points

11
The control panel provides eight on-board points (Terminals 11 to 22). Each point functions
independently and does not interfere with the operation of the others. The control panel
monitors the sensor loops for normal, shorted, or open conditions between an input terminal
and any of the point common terminals.
The programming for the point determines how the control panel responds to those
conditions.
The control panel ignores sensor loops (both on-board and off-board) for 60 seconds after
power up to ensure that any connected devices stabilize.
Caution!
Any points programmed as fire supervisory points are latching. A latching point requires
!
acknowledgment before it can be cleared.
12.1

Point sensor loops

You can configure each sensor loop for a single EOL resistor, or for dual EOL resistors. Single
EOL resistor is the default. For dual EOL resistors, set the Point Index (point profile) > Circuit
Style parameter to dual.
Notice!
You do not need to install the EOL resistor for unused points (Point Index parameter set to 0
[zero]).
UL does not permit normally closed loops for commercial fire applications.
Notice!
Optionally use these points for household fire applications. You can connect four-wire
detectors to these points, for example.
12.1.1

Single EOL (and no EOL) resistor circuit style

When wiring on-board points for the single EOL resistor circuit style, install the resistor at the
far end of the sensor loop to provide a reference for supervision. You can connect dry contact
sensing devices in series (normally closed) or in parallel (normally open) to any of these loops.
The number of normally open and normally closed detection devices each sensor loop can
supervise is limited only by the resistance on the loop. The total resistance for the wire length
and contacts, excluding the end-of-line (EOL) resistor, must not exceed 100 Ω.
2016.06 | 08 | F.01U.303.996
12
13
14
Installation and System Reference Guide
15
16
17
Control Panels
18
19
20
Bosch Security Systems, Inc.
21
22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B9512g-eB8512g-eB8512g

Table of Contents