Connecting To Sa100/Sa200; Connecting To X-Tio Module - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

9.5.14 Connecting to SA100/SA200

Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps, 19200bps
Communication speed
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
[8E1]: 8bit, Even, 1bit
Data bit configuration
[8E2]: 8bit, Even, 2bit
(Data bit, Parity bit, Stop bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address
1 to 99
(Slave address)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.

9.5.15 Connecting to X-TIO Module

(1) Communication settings
Make the communication settings of the temperature
controller.
Item
*1
9600bps, 19200bps, 38400bps
Communication speed
Communication protocol
MODBUS
Data bit: 8bit, Parity: None
Data bit: 8bit, Parity: Even
Data bit configuration
Data bit: 8bit, Parity: Odd
Stop bit: 1bit (fixed)
*2
1 to 99
Module address
When combining the module, turn ON the
Internal data bus
internal data bus terminating resistor at both
terminating resistor
ends of the module.
Data interval extension
0 to 99ms
time
*1
Adjust the settings with GOT settings.
*2
When the setting value is set to 0, a communication is not
made.
9 - 46
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
Setting range
*4
Setting range
(2) Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol.
Setting item
Set value
1
9600bps
ON OFF
Communicati
19200bps
OFF ON
on speed
38400bps
ON
Data bit: 8bit,
Parity: None
Data bit
Data bit: 8bit,
configuration
Parity: Even
Data bit: 8bit,
Parity: Odd
Communicati
MODBUS
on protocol
Internal data
OFF
bus
termination
resistor
ON
setting
Data interval
extension
0 to 99ms
time
(3) Module address settings
Set the unit address using the rotary switch (address
setting switch).
(Address setting switch)
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
Dip switch
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Switch position
2
3
4
5
6
7
ON
ON OFF OFF
ON OFF ON
ON
ON
ON
ON
ON OFF ON
Rotary switch
Upper digit setting
(Set value x10)
Lower digit setting
(Set value x1)
ON
OFF
8
OFF
ON