Siemens sinamics G120 Operating Instructions Manual page 226

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Advanced commissioning
6.5 Motor control
Default setting after selecting the application class Standard Drive Control
Selecting application class Standard Drive Control in the quick commissioning adapts the
structure and the setting options of the U/f control as follows:
● Starting current closed-loop control: At low speeds, a controlled motor current reduces
the tendency of the motor to oscillate.
● With increasing speed, transition from closed-loop starting current control into U/f control
with voltage boost depending on the load.
● Soft starting is not possible.
● Fewer parameters
Image 6-35
The complete function diagrams 6850 ff. for application class Standard Drive Control are
provided in the List Manual.
226
Default setting of the U/f control after selecting Standard Drive Control
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit