Advanced commissioning
6.2 Inverter control
6.2.5

Two-wire control, method 2

You switch the motor on and off using a control command (ON/OFF1) and at the same time
select clockwise motor rotation. You also use the other control command to switch the motor
on and off, but in this case you select counter-clockwise rotation for the motor.
The inverter only accepts a new control command when the motor is at a standstill.
Image 6-6
Table 6- 8
ON/OFF1
clockwise rota-
Parameter
p0015 = 17
Advanced setting
Interconnecting control commands with digital inputs of your choice.
p3330[0 ... n] = 722.x
p3331[0 ... n] = 722.x
166
Two-wire control, method 2
Function table
ON/OFF1 coun-
ter-clockwise
tion
rotation
0
0
1
0
0
1
1
1
Description
Macro drive unit
Controlling the motor using the
digital inputs of the inverter:
BI: 2/3 wire control command 1 (ON/OFF1 clockwise rotation)
BI: 2/3 wire control command 2 (ON/OFF1 counter-clockwise rotation)
Example: p3331[0] = 722.0 ⇒ if CDS 0 (index[0]) is selected, the inverter
receives its ON/OFF1 counter-clockwise command via DI 0.
Function
OFF1: The motor stops.
ON: Clockwise motor rotation.
ON: Counter-clockwise motor rotation.
ON: The motor direction of rotation is based on the signal that
assumes status "1" first.
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
DI 0
DI 1
ON/OFF1 clock-
ON/OFF1 coun-
wise rotation
ter-clockwise
rotation